8

Instruction Booklet 

IB0191004EN

Effective June 2020

EAFR-110PLV current and arc light 

sensor relay user manual 

  

EATON

 www.eaton.com

3.6 Dipswitch settings

The EAFR-110PLV functionality, such as tripping logic, is configured 

using the dipswitch settings.  The relay contains two switch groups 

SW1 and SW2 (see Figure 4).  The dipswitches are located at the 

back of the relay for easy access.

Figure 4. EAFR-110PLV dipswitches SW2 and SW1.

Different trip configurations can be easily programmed by selecting 

the appropriate dipswitch settings.  The most convenient way to 

set the EAFR-110PLV single relay or more complex arc protection 

system is to use the Standard Arc Schemes for Arc Quenching 

Switchgear.  For different arc schemes applications, see the Standard 

Arc Flash Relay Schematics for Arc Quenching Switchgear manual 

(IB0191003EN).
Tripping may be selected based on arc light only or current thresh-

olds.  Other tripping criteria, such as under-voltage or similar, may 

be applied instead of over-current as well using binary inputs.  The 

circuit breaker failure protection (CBFP) configuration may also be 

enabled using the dipswitches.  See Table 2: EAFR-110PLV Dipswitch 

SW1 Setting and Table 3: EAFR-110PLV Dipswitch SW2 Setting for 

details of settings.

Table 2.  EAFR-110PLV dipswitch SW1 setting.

Dipswitch

Function selection

ON (Left Position)

OFF (Right Position)

8  

S1: Light / Light + Current

Sensor channel 1 trip criteria.

Trip on light only.

Trip on light and over-current.  Both signals are required 

simultaneously to trip.

7  

S2: Light / Light + Current

Sensor channel 2 trip criteria.

Trip on light only.

Trip on light and over-current.  Both signals are required 

simultaneously to trip.

6  

SX: Light / Light + Current.

Sensor channels 3 - 5 trip criteria (channel 3 in 

 EAFR-110F)

Trip on light only.

Trip on light and over-current.  Both signals are required 

simultaneously to trip.

5  

a/b

Selection of standard arc configuration type.

Standard arc configurations type a. Standard arc configurations type b.

4  

Configuration select

Selection of standard arc configuration.

Refer to IB0191003EN.

Refer to IB0191003EN.

3  

Configuration select

Selection of standard arc configuration.

Refer to IB0191003EN.

Refer to IB0191003EN.

2  

Configuration select

Selection of standard arc configuration.

Refer to IB0191003EN

Refer to IB0191003EN

 Configuration select

Selection of standard arc configuration.

Refer to IB0191003EN

Refer to IB0191003EN.

Table 3.  EAFR-110PLV dipswitch SW2 setting.

Dipswitch

Function selection

ON (left position)

OFF (right position)

8  

T1/T2: latch/non-latch

Latch or non-latch for trip relays T1 and T2.

T1 and T2 operate as latched.

T1 and T2 operate as non-latched.

7  

HSO: latch/non-latch

Latch or non-latch for HSO1 and HSO2.

HSO1 and HSO2 operates as latched. HSO1 and HSO2 operates as non-latched.

6  

S1: TBD

Reserved for future use.

N/A

N/A

5  

S5: N/A

Arc quenching device output

N/A

Enables arc quenching device output.  Switch should 

always be set to this position.

4  

Fast / CBFP

Selection of trip relay T2 function.

Trip relay T2 will have 7 ms trip time. Trip relay T2 will work as CBFP relay.  If any sensor 

or light input (BI2) is activated for more than the 

set CBFP time (100 or 150 ms), the CBFP function 

activates the trip relay T2 and binary output BO1. 

Note:

 Master trip command (BI2, see dipswitch 4) 

will not activate T2 when in CBFP mode

3  

100 / 150 ms

CBFP time setting.

CBFP time is set to 100 ms.

CBFP time is set to 150 ms.

2  

Phase sensor: 1A / 5A

Phase currents IL1, IL2, and IL3 nominal current 

selection.

1A nominal current.

5A nominal current.

1  

Earth Ground sensor: 1A / 5A

Earth current ground sensor nominal current 

selection.

1A nominal current.

5A nominal current.

Содержание EAFR-110PLV

Страница 1: ...eneral 2 3 Operation and configuration 5 4 Arc sensors 9 5 System self supervision 11 6 Connections 12 7 Wiring diagrams 13 8 Dimensions and installation 14 9 Testing 16 10 Troubleshooting guide 19 11...

Страница 2: ...uP Microprocessor 2 General The Eaton Arc Flash Relay EAFR 110PLV is a sophisticated micro processor based arc flash protection relay with combined current and arc sensing Combined current and arc se...

Страница 3: ...vice AQD for the maximum level of arc fault protection The main features of EAFR 110PLV 110 220 Vac 125 250 Vdc auxiliary power supply Three phase current inputs IL1 IL2 and IL3 1A 5A nominal One grou...

Страница 4: ...supervision Control and power supply Ig X3 12 11 10 9 8 7 6 5 4 3 2 1 1A 5A HSO1 1A 5A 1A 5A 1A 5A HSO2 T3 SW1 SW2 set x In Ig set x In Current 0 5 0 05 1 0 6 0 13 12 S1 S2 8 7 6 S3 5 4 3 S4 2 1 QD u...

Страница 5: ...ve condition If the arc sensor is activated the corresponding sensor channel LED will turn on if the activation is longer than 1 5 ms The sensor LED activation function is latched steady light To clea...

Страница 6: ...formed Also activated by pressure information Check why the sensor activated check the sensor continuity or perform system setup see Section 3 3 1 Auto configuration System setup S4 Amber Normal statu...

Страница 7: ...n previous memorized set up a dip switch anyone must be moved back and forth prior to performing auto configuration Timeout allowing new configuration is one minute Reconfiguration with more connectio...

Страница 8: ...trip criteria channel 3 in EAFR 110F Trip on light only Trip on light and over current Both signals are required simultaneously to trip 5 a b Selection of standard arc configuration type Standard arc...

Страница 9: ...as completely as possible One sensor per closed metal clad compartment should be utilized In open spaces such as the bus bar section arc sensors should be mounted maximum 2 m 6 5 ft apart The factory...

Страница 10: ...see Figure 8 Figure 8 EAFR 01 sensor connection step 2 3 Connect the other end of the cable to a sensor channel on the EAFR 101 or EAFR 110PLV relay see Figure 9 Figure 9 EAFR 01 sensor connection ste...

Страница 11: ...the ERROR LED is illuminated If a fiber sensor failure occurs the unit will go into Error mode The ERROR LED will turn on the SF relay will release and the corresponding faulty fiber sensor channel L...

Страница 12: ...gized again 6 2 Inputs 6 2 1 Current measurement inputs The EAFR 110PLV has four CT inputs for three phase current and earth current measurement Both phase current and earth current inputs may be conf...

Страница 13: ...iring diagrams Figure 17 EAFR 110PLV wiring diagram A A T2 CBFP T3 SF T1 T4 X2 1 2 13 12 11 10 9 8 7 6 X1 11 10 9 8 7 6 5 4 3 2 1 UAUX S1 S2 S3 S4 S5 Station battery _ EAFR 110PLV _ _ _ IL1 IL2 IL3 Ig...

Страница 14: ...t sensor relay user manual EATON www eaton com 8 Dimensions and installation The EAFR 110PLV is door mounted in standard 19 in 482 6 mm rack height of 4U and 1 4 of a relay wide Figure 18 EAFR 102 dim...

Страница 15: ...Figure 19 EAFR 110PLV dimensions in millimeters inches 3 D view POWER ERROR TRIP 1 TRIP 2 SEN 1 SEN 2 SEN 3 SEN 4 FIBER I IN L OUT M TRIP L1 L2 L3 Io BO1 BO2 ARC PROTECTION SET AQ 1 10 157 6 18 82 3 2...

Страница 16: ...corresponding sensor channel indication LED status is changed to ON 4 Verify the relay output s activation s by checking the circuit breaker status or by monitoring the trip contact status The circuit...

Страница 17: ...d configured to send light information 13 Press the SET push button to reset all indications and latches 14 If the binary input BI2 is utilized for master trip to activate the BI2 verify that a trip h...

Страница 18: ...s Sensor channel 1 setting Sensor channel 2 3 4 setting Circuit breaker failure protection CBFP in use yes no Object activated LED indication T1 and T2 active BO1 active Sensor channel 1 Sensor 1 Sens...

Страница 19: ...stance 10 m Power consumption of current inputs circuit 10 m 11 4 Trip relays T1 and T2 Number 3 NO 1 NC or 4 NO Rated voltage 250 Vac dc Continuous carry 5 A Make and carry for 0 5 s 30 A Make and ca...

Страница 20: ...degree back IP 20 Dimensions W x H x D mm W x H x D in 102 x 157 x 164 mm 4 02 x 6 18 x 6 46 in Package dimensions W x H x D mm in 230 x 120 x 210 mm 9 06 x 6 18 x 6 46 in Weight 0 7 kg 24 69 oz 1 0...

Страница 21: ...or 20 m 65 62 ft EAFR 06 25 65C2013G04 Arc light plastic fiber sensor 25 m 82 02 ft EAFR 06 30 65C2013G05 Arc light plastic fiber sensor 30 m 93 43ft EAFR 06 35 65C2013G06 Arc light plastic fiber sens...

Страница 22: ...ement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOS...

Отзывы: