3 Installation
3.3 Flush mounting in control panel
70
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
3.3.2.2 Fitting on mounting plate
The DS7 soft starters are screwed onto the switch cabinet wall (mounting
plate). The control signal terminals and the operator control and display
elements must face the front. The screw fixing is completed with at least
two diagonally arranged flat head screws. The use of washers and split
washers is recommended.
Figure 51: Screw fixing on mounting plate (example using size 1)
Size 1 (up to 12 A)
Size 2 (up to 32 A)
Figure 52: Drilling dimensions
⌀
4.2 mm
(0.17")
l ≧
16 mm
(l ≧ 0.63")
2 x M4
1.3 Nm
(11.50 lb-in)
4 x M4
122 mm
35 mm
(4.8")
(1.38")
2 x M4
140 mm
35 mm
(1.38")
(5.51")
Содержание DS7 Series
Страница 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Страница 4: ...II...
Страница 14: ...0 About this Manual 0 8 Units of measurement 10 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 64: ...2 Engineering 2 15 Example of other load cycles 60 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 122: ...6 Parameterization 6 2 Default settings of the basic device 118 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 148: ...7 Connection examples 7 3 Size 3 and 4 41 200 A 144 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...