8.9.3.11 Profile 10: Outputs (control)
Output bytes 0 and 1 (Short) are mapped as follows on SmartWire-DT.
Table 37: Profile 10: Output bytes 0 and 1
Byte 1 is only needed for internal SmartWire-DT-specific functions.
Byte
Bit
Designation
Meaning
0
(Control
DS7)
0
EN_Set
Enable Setpoint, DS7 Start/Stop:
EN_Set enables the setpoint value and starts or
stops the motor with the ramp function.
0: (deactivate setpoint value)
1: (activate setpoint value)
1
–
Not used
2
EN_Op
Operation released:
0: Stop (immediate disconnection of the output)
1: Operation
3
FaultAck
Fault Acknowledge
0: Do not acknowledge current fault
1: Acknowledge current fault (rising edge: 0
→
1)
4 - 7
–
Not used
1
0 - 7
–
Not used
Содержание DS7 Series
Страница 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Страница 4: ...II...
Страница 14: ...0 About this Manual 0 8 Units of measurement 10 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 64: ...2 Engineering 2 15 Example of other load cycles 60 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 122: ...6 Parameterization 6 2 Default settings of the basic device 118 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 148: ...7 Connection examples 7 3 Size 3 and 4 41 200 A 144 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...