8 SmartWire-DT
8.9 Programming
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
177
8.9.3.9 Profiles 7, 8, 9: Outputs (control)
Output bytes 0 and 4 are mapped as follows on SmartWire-DT.
Profiles 7, 8, and 9 correspond to profiles 1, 2, and 3, but with two added
words:
Profile 4 = Profile 1 (2 bytes) + DS7 status (2 words)
Table 35: Profiles 7, 8, 9: output bytes 0 and 4
Byte
Bit
Designation
Meaning
0
See: Profile 1 – 3: Output byte 0
+2 (DS7 status)
0
OnOff
Switch on/off
0: Normal stop (with configured ramp time)
1: Operation
1
Off2
Run-down (Coast Stop: Off 2)
0: Coast stop (switch off output voltage)
1: no free run-down
2
Off3
Quick Stop: Off3
0: Quick stop (shortest ramp)
1: no quick stop
3
EN_Op
Operation released
0: Stop
1: Operation
4
EN_Ramp
Enable Ramp
0: Reset ramp (setpoint value = 0)
1: Release ramp
5
Unfreeze
Unfreeze ramp
0: Freeze ramp (the ramp generator’s current output value will be frozen)
1: Do not freeze ramp
6
EN_Set
Enable Setpoint, DS7 Start/Stop:
EN_Set enables the setpoint value and starts or stops the motor with the
ramp function.
0: Do not activate setpoint value
1: activate setpoint value
7
FaultAck
Fault Acknowledge
0: Do not acknowledge current fault
1: Acknowledge current fault (rising edge: 0
→
1)
8
–
Not used
9
–
Not used
10
Ctl_PLC
PLC assumes control (Control by PLC)
0: no control via PLC
1: Control via PLC
11 - 14
–
Not used
15
ExtFault
External Fault
If the bit is set, the DS7 will stop with a selected PNU 840 function.
The behavior is the same as if there were a change from 1
→
0 in the Enable
signal, with the exception that the DS7 soft starter will switch to the
Error status (input bytes n + 4: bit 3).
The external fault can be reset just like any other fault (with Fault
acknowledge (bit 7) or by switching the supply voltage off and on).
0: no external fault
1: external fault
+2 (reserved)
0 - 15
Not used
Содержание DS7 Series
Страница 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Страница 4: ...II...
Страница 14: ...0 About this Manual 0 8 Units of measurement 10 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 64: ...2 Engineering 2 15 Example of other load cycles 60 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 122: ...6 Parameterization 6 2 Default settings of the basic device 118 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 148: ...7 Connection examples 7 3 Size 3 and 4 41 200 A 144 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...