8 SmartWire-DT
8.9 Programming
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
175
8.9.3.7 Profiles 7, 8, 9: Inputs (status)
Input bytes are mapped as follows on SmartWire-DT.
Table 34: Profiles 7, 8, 9: Input bytes
Byte
Bit
Designation
Meaning
0
section 8.9.3.2, “Inputs (status) pro
1
2
3
4
+2 (Long)
0
RSO
Ready to switch on: S2
0: Not ready for switching on
1: Ready for switching on
1
RDY
Ready to operate; switched on: S3
0: not ready for operation
1: ready for operation
2
EN
Operation (Enabled S4)
0: Stop
1: Operation
3
ERR
Error present (Error)
0: no error
1: Error
4
C_Stop
Free run-down, output de-energized (coast stop)
0: no free run-down
1: free run-down
5
Q_Stop
Quick stop, shortest ramp
0: no quick stop
1: Quick stop
6
SOI
Reclosing lockout (switching on inhibited: S1)
0: No switch-on inhibit
1: Switch-on inhibit
7
WARN
Warning present:
0: no warning
1: Warning
8
RUN
DS7 Run, power part active
0: Stop (power section inactive)
1: Running (power section active)
9
Ctl_Req
Control requested to PLC
Is set if PNU 928.0 = 1.
0: Not ready for remote control
1: Ready for remote control
10
TOR
Top of ramp:
0: Top of start ramp not reached
1: Top of start ramp reached
11
1)
CL
Current limit:
0: Current limit not reached
1: Current limit reached
12
–
Not used
+2 (Long)
0 - 15
Utilization (Int16)
Load as a percentage (utilization %):
LB: Low Byte / HB: High Byte
0 - FFFF
≙
±200 % / 0x4000
≙
±100 %
1) Bit 11 will only be activated if parameter 681.0 is set to 1.
Содержание DS7 Series
Страница 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Страница 4: ...II...
Страница 14: ...0 About this Manual 0 8 Units of measurement 10 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 64: ...2 Engineering 2 15 Example of other load cycles 60 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 122: ...6 Parameterization 6 2 Default settings of the basic device 118 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 148: ...7 Connection examples 7 3 Size 3 and 4 41 200 A 144 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...