8 SmartWire-DT
8.9 Programming
188
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
362
0
rw
ComLoss/Timeout
T2
Time before automatic switch-off
10 - 300
10
514
1
ro
IeBreaker
Unsigned16
Current PKE current:
Corresponds to I_REL of the cyclic
input data with an expanded value
range
0 - 800 %
0 - 65535
0
681
0
rw
SetCurrentLimit
Unsigned8
Used to enable PKE current
limitation:
0: Current limitation deactivated
1: Current limitation activated
0; 1
0
723
0
ro
OverloadStatus
Unsigned8
Overload status:
0: No overload
1: Overload (main alarm)
0; 1
0
723
1
ro
OverloadLimitStatus
Unsigned8
Overload limit status:
The overload limit status is based
on PNU 823.1
0: Overload limit not reached
1: Overload limit reached
→
Potential impending overload fault
(Early-warning)
0; 1
0
750
0
ro
InputStatusA1
Unsigned8
Current status of control signal
terminal A1:
0: Voltage unavailable
1: Voltage available
0 - 256
–
750
1
ro
InputStatusEN
Unsigned8
Current status of control signal
terminal EN:
0: Voltage unavailable
1: Voltage available
0 - 256
–
751
0
ro
RelaisStatusTOR
Unsigned8
TOR relay status:
0: not activated
1: activated
0 - 256
0
751
1
ro
RelaisStatusRUN
Unsigned8
RUN relay status:
0: not activated
1: activated
0 - 256
0
820
0
ro
StartCounter
Unsigned32
Counter for the number of starts
0 - (2
32
- 1)
–
821
0
ro
RunTime
T4
Service life counter (RUN):
Counts how long the DS7-SWD
soft starter is switched on (RUN)
0 - (2
32
- 1)
–
821
2
ro
PowerOnTime
T4
Mains voltage counter:
Counts how long mains voltage
(L1, L2, L3) is applied at the DS7-
SWD soft starter
0 - (2
32
- 1)
–
821
1
ro
SupplyOnTime
T4
Supply duration counter:
Counts how long control voltage
(24 V via terminal or SmartWire-
DT) is applied
0 - (2
32
- 1)
–
822
0
ro
HeatsinkTemp
Integer16
Heat sink temperature
-255 - +255 °C
-32767 - 32767
0 °C
0
PNU
Index
PNU
Sub-
index
Access
rights
Designation
Data type
Meaning
Value range
DS
User
setting
Содержание DS7 Series
Страница 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Страница 4: ...II...
Страница 14: ...0 About this Manual 0 8 Units of measurement 10 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 64: ...2 Engineering 2 15 Example of other load cycles 60 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 122: ...6 Parameterization 6 2 Default settings of the basic device 118 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 148: ...7 Connection examples 7 3 Size 3 and 4 41 200 A 144 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...