2 Engineering
2.12 Loading conditions
56
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
2.12.4 Configuration options of DS7
Table 10: Configuration options
Special feature
Configuration
Current
Starts
per hour
Applicable graph
Stand-alone setup
without
internal fan
Standard setup
DS7
Rated operating current I
e
stated on the device applies.
10
The graph applicable to this
load cycle (10 starts per hour)
applies.
→
Stand-alone setup
of sizes 1 and 2
with
internal fan
Increased number of
startups
DS7 (to 32 A)
+ DS7-FAN-032 (fan)
Rated operating current I
e
stated on the device applies.
40
The graph applicable to this
load cycle (10 starts per hour)
applies.
The number of starts per
hour must be multiplied by
the factor 4, i.e.
1, 10, 20
→
4, 40, 80
→
Example II. (page 58)
Assembly with
xStart components
without
fan
Derating required
DS7 (to 32 A)
+ PKZM0-XDM12 or
PKZM0-XM32DE, PKZ/PKE
DILM12-XMCP/T or
ZB…12/ZB32…
The next lower rated
operating current I
e
. applies.
10
The valid graph for the
corresponding next smaller
device type applies.
2)
→
Assembly with
xStart components
with
fan
No derating required
DS7 (to 32 A)
+ PKZM0-XDM12 or
PKZM0-XM32DE, PKZ/PKE
DILM12-XMCP/T or
ZB…12/ZB32…
+ DS7-FAN-032 (fan)
The rated operational
current I
e
stated on the
device applies.
10
The graph applicable to this
load cycle (10 starts per hour)
applies.
→
Example IV. (page 58)
• Increased number
of startups
• Derating required
DS7 (to 32 A)
+ PKZM0-XDM12 or
PKZM0-XM32DE, PKZ/PKE
DILM12-XMCP/T or
ZB…12/ZB32…
+ DS7-FAN-032 (fan)
The next lower rated
operating current I
e
. applies.
40
The valid graph for the
corresponding next smaller
device type applies.
2)
The number of starts per
hour must be multiplied by
the factor 4, i.e.
1, 10, 20
→
4, 40, 80
→
Содержание DS7 Series
Страница 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Страница 4: ...II...
Страница 14: ...0 About this Manual 0 8 Units of measurement 10 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 64: ...2 Engineering 2 15 Example of other load cycles 60 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Страница 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...