Amended: Jan 2014 

 

 

 

“Earth Fault” 

 

An earth fault may be associated with other faults or random fires.  
This should be cleared before trying to sort out these other faults as it may be the root cause. 

Power down the panel, disconnect all loops, sounders and relay connections. Ensure the panel is 
correctly earthed. 
Check the +ve & -ve cables to screen/earth, ensure greater than 1 Mohm. Check that the screen is 
not tied to building earth.  
Repower the panel if the fault remains with the cables disconnected, examine the Pcb’s for 
contaminants or shorts.  

 

“Sounder 1 or 2 Fault” 

 

This is a fault on one of the two conventional sounder channels. Common causes would be:- 
 
One of the fuses has blown. 
 
End of line resistor not fitted. 
 
Sounder wired incorrectly. See wiring diagram. 
 

 

Sounder circuit is shorted. 

 
 

“FRE, FPE, Fault relay Fault” 

 

These are the other panel outputs, faults on these could be:- 

 

End of line resistor not fitted. 
 
Output line is shorted. 

 
 

The panel fails to auto-learn past a device 

 

This may be seen with short or open circuit on the loop, the problem will probably be located at the 
last device detected or the next one along. See the above on open circuit positive/negative.  
If there is no associated open circuit the device may be faulty, link out the device after the last one 
auto-learned and try again. If this fails link out the last device detected and auto learn again. If either 
device is causing the problem replace it. 
Once the faults have been removed from the panel and it shows system healthy after a reset go to the 
system details screen and check the numbers of devices on each loop is the same as what has been 
installed on each loop (spur isolators do not show on system details). If this number is less than 
expected the following may be the cause:- 
 
If spur isolators are fitted the spurs may not be correctly installed. To check this do test device on 
what should be the last device on each spur (see locating a fault below), if the incorrect device LED is 
on work back along the spur with test device until a device is correctly identified. The problem may be 
that device or the next one along the spur, see open circuit negative/positive above. 
If no spur isolators are present or the spurs are all working ensure the site devices have all been 
connected to the loop.  

Содержание DF6000

Страница 1: ...1 Amended Jan 2014 DF6000 Applications Guide...

Страница 2: ...e 10 12 Weekly Test 10 13 Sounder Level Test 10 14 One Man Walk Test 11 15 Test Device 11 16 Disable all Outputs 11 17 Auto Learn 11 18 Analogue Level 12 19 Printer Settings 12 20 Programming I O and...

Страница 3: ...cillary Devices 40 34 Conventional and Addressable Hybrid 46 35 Getting Started Fault Diagnosis 51 36 Commissioning 53 37 Other Faults 60 38 Programming Issues 61 39 Program Updates 62 40 Panel Comm 6...

Страница 4: ...Pages 39 40 Download analogue level Log to PC 20 Aug 09 Page 10 Pre Addressed Autolearn 20 Aug 09 Pages 11 12 13 Programming I O Sounders Sub Menus 06 Oct 09 Page 35 Boot up error codes 16 Jul 10 Page...

Страница 5: ...ones Daylight savings BS5839 Jan 12 Pages 22 27 42 Zone groups high level menus Repeaters May 12 Page 10 39 Maintenance Autolearn ULMCOM S Jul 12 Pages 25 34 43 47 Network programming Networking Hybri...

Страница 6: ...6 Amended Jan 2014 Menu Structure User Access Code FIG 1 Engineers Menu FIG 2...

Страница 7: ...n 60 Sounder Beacon MIO single and 3 chan 20 3 Chan I O MCOM 20 3 Chan I O MCOMS 60 Sounder Beacon Uses 1 sounder channel MCOM R 20 3 Chan I O MCIM old version 20 3 Chan I O Obsolete MCIM C 200 Callpo...

Страница 8: ...r parts of the menu which are used for learning and programming the system High Level Codes These 2 codes give access to menu s which 1 Can be used to return the system to its factory settings and to...

Страница 9: ...nd is must be programmed on stage 1 of Device Outputs The maximum time is ten minutes and it can only be programmed in whole minutes When programming a delay on the panel sounder circuits the zones se...

Страница 10: ...dition but one fire from outside the list will also satisfy the output condition This function is similar to double knock in the way that it is set up i e by address by zone and has the same restricti...

Страница 11: ...s a second loop to be learned without having to relearn Loop 1 If a second loop controller is installed then the option to learn loops 3 4 individually is displayed Pre Addressed Autolearn has been ad...

Страница 12: ...n this screen 1 Panel Outputs The only sounder programming which can be changed on the panel is the sounder tone and the volume if these settings are changed then the changes are applied to all the so...

Страница 13: ...l revert back to the site installer program plus any programmed delays Both must be set if either is reqd Both of these delays can be overridden by the operation of a Callpoint or the input of an I O...

Страница 14: ...Auto enable delays This feature enables the user to automatically set T1 T2 at the required times as a backup if the input is missed A more recent amendment July 2011 has introduced an automatic disab...

Страница 15: ...which external outputs should respond to the T1 T2 time delays This feature is programmed through the device outputs dialog within the Site Installer program All external output devices are defaulted...

Страница 16: ...The re configured screen gives the Fireman controls to silence the alarms mute buzzer and reset the panel without having access to the pass code Swedish mode is very similar except that the panel must...

Страница 17: ...lectronic sounders during an alarm situation but go to bell tone when class change is operated This feature is at odds with the HMO settings above so the panel must be informed if these sounders are i...

Страница 18: ...ton Synch with master has been added to automatically synchronise the time with the master panel which in this case is always panel number 1 Configure Zones Following an Autolearn all devices are by d...

Страница 19: ...ogramming list to include non fire input FRE only activate or Extinguisher only activate The input programming can also be used to turn on and off the feature T1 T2 When disable addresses is used on t...

Страница 20: ...ly by zone by address or by panel Each output can have three stages programmed whatever is set in each stage that matches the input trigger the output will follow there is no designated hierarchy Howe...

Страница 21: ...ntrol an output then the other 2 stages can be used to increase the allocated zones For example Stage 1 can have zone 1 16 stage 2 can have zones 17 32 and stage 3 can have zones 33 48 The sounder wil...

Страница 22: ...oftware JUL 2011 250 Zone groups have been added to the system so that when any output devices trigger source is by zone this now becomes by zone group Each zone group can contain up to 32 traditional...

Страница 23: ...adically improved in the previous version only one zone was allowed in the assigned zone groups In this latest version the number allowed has been increased to 16 zone groups and 32 zones within a zon...

Страница 24: ...ked this device would follow the normal program this is particularly useful on a beacon which is used to warn the operator of an alarm situation before T1 T2 has a chance to time out The second is use...

Страница 25: ...dba at the bedhead In this instance individual sounder volumes can be programmed through the site installer program to prevent the panel from becoming overloaded This is achieved by a right click on...

Страница 26: ...as been added then it will be placed in zone 1 it then needs to be assigned to the correct zone and have text inserted Sounders and I O units can be added but on the older software will not operate so...

Страница 27: ...total number of panels that are connected on the network Panel 1 is automatically configured as the master such that if a network fault occurs the master and faulty panel only will display the Lon Ne...

Страница 28: ...hen on the input programming menu you tick the day night box Then you go to either thermal or photo thermal detectors and on the input programming menu you tick day night mode When you tick day night...

Страница 29: ...e engineer leaves site the user can re enable the outputs from the enable disable menu in 2214 or on later versions simply toggle the button in the high level menu On release version Jul 12 when all d...

Страница 30: ...ows the engineer to change the Logo shown on the front screen of the panel Customers can also download their own logo into the panel from the Commissioning menu The logo must be configured as a Monoch...

Страница 31: ...n on the screen Autolearn Locking This feature has been added to prevent malicious or untrained personnel initiating an Autolearn once the system has been commissioned Evacuate Locking Evacuate once i...

Страница 32: ...ircuits become Notification appliance circuits NACS and the Loops Signal line circuits SLC The Mute buzzer is acknowledge alarm and as a UL requirement the buzzer also re starts after 8 hours if the p...

Страница 33: ...ect for output devices will only follow when the time to process this is available Local Zones Generally UK networks use global zones where all zones for the whole network appear on all panels In this...

Страница 34: ...part 13 Fast Automatics The introduction of a more robust response to electrical noise on the loop wiring has slightly slowed the response of smoke detectors on larger loops Whilst still within the re...

Страница 35: ...to ANY fire anywhere on a network To that end a measure of control has been added so that the conventional sounders will only sound when there is an alarm situation on the panel they belong to Pulse...

Страница 36: ...Each panel must have a Self Addressing Network Card fitted to the main PCB Network Technology used is LonWorks Protocol FIG 32 FIG 33 Draka 910234 Network Cable Terminator resistors 2 x 51 in series R...

Страница 37: ...connection point at the first panel and not at any other point The screen or drain wire of the network cable should not be considered as a safety earth and therefore should not be connected to the ter...

Страница 38: ...38 Amended Jan 2014 Fig 35 Network configuration without Boosters Loop Topology Fig 36...

Страница 39: ...twork card is provided Essentially this device enables the connection of a second network on a card running in parallel with the existing network This system is configured in the same way as the norma...

Страница 40: ...are used primarily for Fire but the Input programming in Site Installer gives the options of setting them to fire fault reset silence pre alarm and evacuate A call point can also be used to initiate...

Страница 41: ...S Identical to the above but this unit is programmed to reply as a sounder the relay contacts on the MCOM S change state on reset the UL version resets on silence These units have been created to enab...

Страница 42: ...is the FX1A and must be fitted even if the sounders are not used MSU 840C This device provides the output to control an extract fan or smoke vent in conjunction with a Fan control unit Fan Controller...

Страница 43: ...r will be displayed on the panel Beam Detector MAB50 100R The reflective beam detector uses one address on the system Initially the unit is autolearned and then aligned using the Dill switches on the...

Страница 44: ...dress and all slaves are connected to this Each one must have a 24v supply The 250 outputs are configured within Site Installer by applying rules to each output The trigger source for the Led or relay...

Страница 45: ...ently been added to the range this device provides 8 outputs and 4 inputs The inputs are pre programmed reset evacuate silence and test The output are programmed in the same manner as the 32 way board...

Страница 46: ...inate selecting add a second time will cause the green led to pulse quickly this means that the hybrid is entering commissioning mode After a short time the green Led pulse will slow to about 1 per se...

Страница 47: ...essed again to extinguish the led and stop the search If there are a number of hybrids one must be set to master and the other to slaves using the jumper J2 on the pcb of the hybrid Following the main...

Страница 48: ...extra functionality such as background and receive signal strengths for the devices viewed from the device or Hybrid FIG 44 Test device can only be carried out using the PC function this does not work...

Страница 49: ...device button on the hybrid which will delet ALL devices from the hybrid The panel would still need to be in the 26 v mode found in the configuration menu of the main panel FIG 46 Once the hybrid has...

Страница 50: ...50 Amended Jan 2014 Device status can be checked by interrogating the protocol and packet error count which is an indication as to the signal quality between the device and hybrid FIG 48 FIG 49...

Страница 51: ...battery fuse replace as necessary If the fuse is OK then the PSU PCB needs replacing Power up the PSU and carefully check the 26V and 26Vraw connectors are at around 26V if they are power down the PSU...

Страница 52: ...attached to the display board Send 7 from a PC to the panel to start the screen calibration routine The touch screen works and is correctly calibrated but I cannot get to the supervisor entry screen T...

Страница 53: ...positive to negative will be in the Mohm region Ensure the screen is continuous around the loop this reading should be approx 10 ohms The screen should not be bonded to building earth Test the loops...

Страница 54: ...system The most likely causes would be Device wired incorrectly See wiring diagram for the device Base continuity switch not opening The switch on the base can occasionally be pushed above the metal...

Страница 55: ...ot cleared from the base see images below INCORRECT CORRECT FIG 53 The detector may be pushed away from the base preventing the switch opening or crushing a contact and thus not receiving power The pa...

Страница 56: ...loops cards or cables from the panel d Re apply the power Mains first then battery the panel will stop resetting e Go to the delete device menu in the engineer menu and delete all the repeaters from...

Страница 57: ...middle of the loop that the loop device isolators have detected and dealt with See short circuit middle below If the loop voltage drops below 18 vDC the devices may reset causing an open circuit nega...

Страница 58: ...hange the motherboard Short circuit middle Device wired incorrectly See wiring diagram Device is drawing too much current A faulty device may draw too much current and be detected as a short Replace t...

Страница 59: ...lem will probably be located at the last device detected or the next one along See the above on open circuit positive negative If there is no associated open circuit the device may be faulty link out...

Страница 60: ...o short or open can be found the problem may be a resetting detector see loop voltage drop above in Open circuit Positive Negative section above Alternatively run the Intermittent fault search in the...

Страница 61: ...define ERR_LINE_SMALL 3 define ERR_PIXEL_LARGE 4 define ERR_PIXEL_SMALL 5 define ERR_RECT_LARGE 6 define ERR_RECT_SMALL 7 define ERR_ARROW_SMALL 8 define ERR_ARROW_LARGE 9 define ERR_ARROW_CODE 10 de...

Страница 62: ...reload the program If this will still not download then check the program or replace the micro 2 If after successful download the panel goes into random fires this is almost always due to an incorrect...

Страница 63: ...red prior to any upgrade The display program can be updated using the Panel Prog program and Hyperlink as follows 1 Connect Laptop to the panel via the serial port 2 Open HyperTerminal program and app...

Страница 64: ...and the sends the new file NOTE This will take up to 5 mins so please ensure during the transfer the laptop does NOT go into hibernate mode otherwise the display will become unrecoverable Following th...

Страница 65: ...is program is capable of communicating with the panel by way of sending commands to perform certain functions or receiving information also on command Once opened the program needs no configuration an...

Страница 66: ...6000 2 Test Screen 3 Touch Screen Test 4 LED Test 5 Spare 6 List CDR 7 Calibrate Screen 8 Screen Dump 9 Watchdog Reset A Reverse video B French C Font test D Animation E Simulate Fire F Backlight on o...

Страница 67: ...new feature is housed in the user menu Proceed as follows to download the information to the Laptop 1 Connect Laptop to the panel via the serial port 2 Open HyperTerminal program and apply a name in...

Страница 68: ...protocol choose Xmodem then hit receive 8 When the receive filename box appears give the file a name and click OK 9 Go to the panel and select Send analogue value or Log to PC choose a loop to be tra...

Страница 69: ...n further enhanced by adding the facility to use Site Installer to achieve the same results 2 Commands have been put into the user menu 2214 Download log to PC and download analogue values to PC Touch...

Страница 70: ...70 Amended Jan 2014 Choose commissiom then retrieve event log When save log as dialog box appears give the file a name and where the file should be saved and hit save FIG 63 FIG 64...

Страница 71: ...71 Amended Jan 2014 FIG 65 Once the file has been downloaded it will be saved as an HTML document available for E Mailing...

Страница 72: ...ed by the 30 min alarm period Terminals Normal State Fault state NC Not connected 0v 26v Raw Any 0v 26v Raw Unregulated supply 27 54 0v 26v Any 0v 26v Regulated supply 27 38 0v Battery Fault Any 0v an...

Страница 73: ...ut 13 6v no fault 0v when in fault 28v Output 28 5v approx with no load Fire P E R E 0 6v no fire 28v when in fire Loops 1 4 0v unused 22v normal 24v in fire 27v during autolearn Sounder 1 4 0 6v moni...

Отзывы: