56
Amended: Jan 2014
The panel constantly resets after auto-learn.
This is a specific dual-addressing fault. Certain combination of devices dual addressing may cause
the panel to think they are a repeater and respond to the responses by constantly resetting.
The following steps should be done to remove this problem.
a. Remove the battery leads and Power down the panel
b. Wait at least 3 mins until all of the internal capacitors have fully discharged
c. Remove the loops cards or cables from the panel.
d. Re-apply the power, Mains first then battery - the panel will stop resetting.
e. Go to the delete device menu in the engineer menu and delete all the repeaters from the
panel.
Locate the dual addressing devices (see below to locate a fault) and fix the problem.
Auto-learn the panel, it should no longer reset, if it does repeat the above and locate any further dual
addressing problem.
If the panel is not in alarm or resetting constantly the other dual addresses can be located by using
the test device in the engineering menu, go to the dual address number
– test device and both
devices will light the Led or sound the sounder etc.