28
Amended: Jan 2014
If the network is such that all messaging needs to be turned off but certain panels need to
communicate directly with each other this can be controlled using the network filtering system where
individual panel messaging can be enabled/disabled across the network.
These features are found in ‘Network’ in the configuration menu.
Extra filtering has been added to enable the user to filter commands (reset, evacuate, silence, mute
buzzer) and Status messaging ( Fires & faults) across the network
FIG 24
Day / Night Settings
This is a function in the panel programming that allows certain devices to change their characteristics
dependant on the time of day. The devices that respond to this programming are the Heat detectors
and Photo thermal.
To program day night mode on the panel you add an input device and then on the input programming
menu you tick the day night box.
Then you go to either thermal or photo thermal detectors and on the input programming menu, you
tick day night mode.
When you tick day / night on an input unit you are controlling when the panel goes into and out of
day / night mode.
When you tick day / night on a detector you are instructing that specific detector to respond to
day / night programming.
NOTES
1. The input unit in question must be either an I/O unit or a Callpoint.
2. If a 3 Chan I/O unit is used only channel 1 can be used for this function (the other
channels will put the panel to full fire.
3. The input unit must be on the same Loop Controller as the devices it is setting to
Day/Night
4. As soon as a Photo thermal has a tick against Day/Night the detector becomes pure
heat (A2S - Fixed Heat 60). Hence the Callpoint or I/O must be operated to return this
device to dual mode.
5. A half moon indication now appears on the screen between the supervisor button an
the clock when day night is in operation.