31
Amended: Jan 2014
Reset to Factory Settings
This feature will restore the panel to it’s factory settings, which on a programmed system is
catastrophic and not to be used lightly.
The panel will go into Autolearn
– losing all programming. It will also re-calibrate the screen and put
the default logo onto the screen.
Sounder 1 & Sounder 2
This menu allows the conventional sounder circuits to be set to continuous or pulsing, delayed or
double knock
Terminology
When the panel goes into Fire the word FIRE or ALARM can be selected to display this as part of the
indication on the screen.
Autolearn Locking
This feature has been added to prevent malicious or untrained personnel initiating an Autolearn once
the system has been commissioned.
Evacuate Locking
Evacuate, once initiated from the panel menu or a programmed input, can operate ALL internal and
external outputs connected to the loop. If the panel is controlling critical systems requiring a double
knock scenario such as a Gas release system this could be immediately overridden by the evacuate
command.
In these instances evacuate would be considered inappropriate, therefore, evacuate can now be
locked to prevent it overriding critical programming.
Activate on Evacuate
FIG 27
This feature allows the user to further filter what is required to operate when Evacuate is not locked.