20
Amended: Jan 2014
Output Programming
Outputs are classed as Sounders/Beacons, I/O units, Sounder Control units and Shop Unit Monitors.
The panel is capable of accepting 120 outputs per loop, (60 Sounders set low) and 20 I/O units (each
I/O automatically takes three channels). Sounder Control and Shop units use sounder channels.
To set the
device outputs right click the device, when the device options box appears choose ‘Device
Outputs’.
The output device can now be programmed to respond to a specific trigger
– globally, by zone by
address or by panel.
Each output can have three stages programmed
– whatever is set in each stage that matches the
input trigger the output will follow (there is no designated hierarchy).
However, if the trigger is ‘Global’ in any stage this will always take precedence unless double knock is
also set.
FIG 13
If the sounder programming is to be the same for every device then hit ‘apply these settings to other
devices’ all of the sounders on the panel will be listed and ‘apply to all’ or apply to selected’ can be hit.
NOTE
1.
A delay can only be programmed onto Output 1 stage 1 of any multi-output device
such as a 3 chan I/O or a Sounder controller.
2.
Double knock and delays need to be on separate stages.