32
Amended: Jan 2014
Australian FB Screen
This enables the screen to show Zone or Address text when in Australian mode (see page 13)
UL 864 9
th
Edition
This is an additional feature to enable the panel to be operated in areas where UL is specified.
Essentially the panel remains the same; however, there are a number of differences in terminology
and minor changes to internal software.
Disablements are now displayed as Supervisory warnings, Faults become Troubles.
Sounder circuits become Notification appliance circuits (NACS) and the Loops, Signal line circuits
(SLC)
The Mute buzzer is acknowledge alarm and as a UL requirement, the buzzer also re-starts after 8
hours if the panel is not reset.
The Callpoint is now a Pull Station.
Earth trouble (fault) now has a separate led indication as well as information on the touch screen and
buzzer sounding.
T1/T2 remains the same feature but is now called ‘Positive alarm sequence’.
Alarm Verification has been slightly enhanced to provide 3 time scales 15, 30 and 60 secs
Daylight Savings
FIG 28
Daylight saving mode which would normally be set for the UK market can now be disabled in the high
level menu.