Eaton 93PM-L 20–200kW (208V) UPS Installation and Operation Manual 164000724—Rev 01
41
Table 14. Input/Output Ratings and Wiring Recommendations: 60–100 kW (Single Input Bypass 220/208)
Basic Unit Rating
Units
Rating 50/60 Hz
kW
60
70
80
90
100
Input and Output Voltage
Volts
220/208
220/208
220/208
220/208
220/208
AC Input to UPS Bypass (Four Wire,
Single-Feed)
Full Load Current: (3) Phases– see
Note, (1) Ground
B
Amps
202
235
269
302
336
Neutral Current
Amps
288
337
385
433
481
Minimum Conductor Size (Phase A, B,
and C)
Number per Phase
AWG or
kcmil
(each)
500 MCM
(1)
4/0
(2)
250 MCM
(2)
300 MCM
(2)
350 MCM
(2)
Neutral Wire Size
Number
AWG or
kcmil
(each)
300 MCM
(2)
350 MCM
(2)
500 MCM
(2)
3/0
(4)
4/0
(4)
Minimum Conductor Size (Ground)
Number
–
AWG or
kcmil
(each)
1/0
(1)
2
(2)
2
(2)
2
(2)
2
(2)
DC Input from External Battery (Line-Up-and-Match Eaton 93PM-L IBC-SW, IBC-LW or IBC-LHW)
For Line-Up-and-Match wiring refer to
Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded
or
Eaton 93PM
Universal Integrated Battery Cabinet Installation Manual-Large and Large High Rate
DC Input from External Battery
(Standalone Eaton 93PM-L IBC)
(1) Positive, (1) Negative, (1) Ground
C
Total Amps
136
158
181
203
226
Minimum Conductor Size (Phase
Positive and Negative)
Number per Pole
AWG or
kcmil
(each)
2/0
(1)
3/0
(1)
4/0
(1)
250 MCM
(1)
300 MCM
(1)
Minimum Conductor Size (Ground)
Number
–
AWG or
kcmil
(each)
4
(1)
4
(1)
2
(1)
2
(1)
2
(1)
AC Output to Critical Load (Four
Wire)
Full Load Current
(3) Phases – see Note, (1) Ground
D
Amps
167
194
222
250
278
Neutral Current
Amps
288
337
385
433
481
Minimum Conductor Size (Phase A, B,
and C, and Neutral)
Number per Phase
AWG or
kcmil
(each)
350 MCM
(1)
500 MCM
(1)
3/0
(2)
4/0
(2)
250 MCM
(2)
Neutral Wire Size
Number
AWG or
kcmil
(each)
300 MCM
(2)
350 MCM
(2)
500 MCM
(2)
3/0
(4)
4/0
(4)
Содержание 93PM-L IAC-B
Страница 1: ...p n 164000724 Revision 01 20 200 kW 208V UPS Installation and Operation Manual Eaton 93PM L UPS ...
Страница 10: ...x Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 List of Tables ...
Страница 112: ...102 Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 UPS System Installation ...
Страница 148: ...138 Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 Communication ...
Страница 154: ...144 Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 UPS Maintenance ...
Страница 158: ...148 Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 Product Specifications ...
Страница 161: ...Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 151 Warranty ...
Страница 162: ...16400072401 164000724 01 ...