Eaton 93PM-L 20–200kW (208V) UPS Installation and Operation Manual 164000724—Rev 01
Table 5. Input/Output Ratings and Wiring Recommendations: 10– 50 kW (208/208) (Continued)
AC Output to Critical Load (Four
Wire)
Full Load Current (3) Phases – see Note,
(1) Ground
D
Amps
28
56
83
111
139
Neutral Current
Amps
48
96
144
192
240
Minimum Conductor Size (Phase A, B,
and C)
Number per Phase
AWG or
kcmil
(each)
8
(1)
3
(1)
1/0
(1)
3/0
(1)
250 MCM
(1)
Neutral Wire Size
Number
AWG or
kcmil
(each)
3
(1)
2/0
(1)
300 MCM
(1)
500 MCM
(1)
4/0
(2)
Minimum Conductor Size (Ground)
Number
–
AWG or
kcmil
(each)
8
(1)
8
(1)
6
(1)
4
(1)
2
(1)
NOTE
Callout letters
A
,
B
,
C
and
D
map to
Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM-L Integrated Battery
Cabinet (IBC).
Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated
UPS kW frame size installed.
Содержание 93PM-L IAC-B
Страница 1: ...p n 164000724 Revision 01 20 200 kW 208V UPS Installation and Operation Manual Eaton 93PM L UPS ...
Страница 10: ...x Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 List of Tables ...
Страница 112: ...102 Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 UPS System Installation ...
Страница 148: ...138 Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 Communication ...
Страница 154: ...144 Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 UPS Maintenance ...
Страница 158: ...148 Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 Product Specifications ...
Страница 161: ...Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 151 Warranty ...
Страница 162: ...16400072401 164000724 01 ...