Eaton 93PM-L 20–200kW (208V) UPS Installation and Operation Manual 164000724—Rev 01
Table 15. Input/Output Ratings and Wiring Recommendations: 110–150 kW (Single Input Bypass 220/208) (Continued)
Minimum Conductor Size (Ground)
Number
–
AWG or
kcmil
(each)
2
(2)
2
(2)
1/0
(2)
1/0
(2)
1/0
(2)
NOTE
Callout letters
B, C
and
D
map to
.
Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM-L Integrated Battery
Cabinet (IBC).
Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated
UPS kW frame size installed.