Eaton 93PM-L 20–200kW (208V) UPS Installation and Operation Manual 164000724—Rev 01
105
•
In Battery mode, the battery provides DC power, which maintains inverter operation. The battery supports
the critical load.
The following paragraphs describe the differences in the UPS operating modes, using block diagrams to show
the power flow during each mode of operation.
55..22..22
EEnneerrggyy S
Saavveerr S
Syysstteem
m M
Mooddee
When the UPS is operating in ESS mode, commercial AC power is supplied directly to the critical load through
the internal bypass with the power module in a standby state. Surge protection and some filtering is also
provided, ensuring that clean power is delivered to the load equipment. If a commercial power brownout,
blackout, overvoltage, undervoltage, out-of-tolerance frequency condition occurs, or any other disturbance is
detected in the incoming power, the system forward transfers to normal mode (double-conversion on
demand). In case of a complete utility outage or if input power is outside the tolerances of the system, the UPS
transfers to battery mode and continues to supply conditioned, clean power to the critical load. When the input
line returns to normal operating range, the UPS returns to ESS operation. For charging batteries, the UPS will
not enter ESS mode until charger is 25% or less of maximum charger current.
When operating in ESS, the UPS superior detection and control algorithms continuously monitor incoming
power quality and allow the fast engagement of power converters. Typical transition time to double conversion
is less than two milliseconds. If the UPS detects a fault condition while operating in ESS, it is also able to detect
and determine whether the fault is caused by the load or if it is upstream from the UPS. A fault at the bypass
source results in an immediate switch over to the inverter; a fault in the load keeps the UPS in Energy Saver
System (ESS) mode.
When power conditions are within acceptable limits, the UPS operates as a high-efficiency, energy-saving
system — providing surge protection for IT equipment and ensuring clean power is delivered to the facility.
Energy saver system increases system efficiency to 99% at 100% linear load and nominal Vin.
shows the path of electrical power through the UPS system when the UPS is operating in Energy
Saver System Mode.
ESS mode is a normal operating mode, and not an alarm condition. While the UPS is in this mode, the
NORMAL light on the front display will illuminate.
Содержание 93PM-L IAC-B
Страница 1: ...p n 164000724 Revision 01 20 200 kW 208V UPS Installation and Operation Manual Eaton 93PM L UPS ...
Страница 10: ...x Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 List of Tables ...
Страница 112: ...102 Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 UPS System Installation ...
Страница 148: ...138 Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 Communication ...
Страница 154: ...144 Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 UPS Maintenance ...
Страница 158: ...148 Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 Product Specifications ...
Страница 161: ...Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 151 Warranty ...
Страница 162: ...16400072401 164000724 01 ...