Eaton 93PM-L 20–200kW (208V) UPS Installation and Operation Manual 164000724—Rev 01
Table 8. Input/Output Ratings and Wiring Recommendations: 160–200 kW (208/208) (Continued)
AC Output to Critical Load (Four
Wire)
Full Load Current (3) Phases – see Note,
(1) Ground
D
Amps
444
472
500
527
555
Neutral Current
Amps
769
817
865
913
962
Minimum Conductor Size (Phase A, B,
and C)
Number per Phase
AWG or
kcmil
(each)
300 MCM
(3)
300 MCM
(3)
350 MCM
(3)
400 MCM
(3)
400 MCM
(3)
Neutral Wire Size
Number
AWG or
kcmil
(each)
4/0
(6)
250 MCM
(6)
300 MCM
(6)
300 MCM
(6)
300 MCM
(6)
Minimum Conductor Size (Ground)
Number
–
AWG or
kcmil
(each)
2
(3)
2
(3)
2
(3)
1/0
(3)
1/0
(3)
NOTE
Callout letters
A
,
B
,
C
and
D
map to
Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM-L Integrated Battery
Cabinet (IBC).
Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated
UPS kW frame size installed.
Содержание 93PM-L IAC-B
Страница 1: ...p n 164000724 Revision 01 20 200 kW 208V UPS Installation and Operation Manual Eaton 93PM L UPS ...
Страница 10: ...x Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 List of Tables ...
Страница 112: ...102 Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 UPS System Installation ...
Страница 148: ...138 Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 Communication ...
Страница 154: ...144 Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 UPS Maintenance ...
Страница 158: ...148 Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 Product Specifications ...
Страница 161: ...Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 151 Warranty ...
Страница 162: ...16400072401 164000724 01 ...