background image

34008030 /AD – Page 1 

1. SOFTWARE UPDATE 

 

Step 1

 

  

             Pulsar MX 4000/5000 RT 

 

                  Pulsar MX Frame 

 

 

 
Connect the RS232 cable to the UPS and serial port of the computer. 
Make sure there are no other software packages utilising the Serial Com port on your computer (like 
PSP or the comm. Modules BIL.exe or CILRS232.exe).

 

 

***IMPORTANT NOTE*** 

1.

 

Make sure that all the computer power saving functions are disabled, like sleep mode or 
screen saver functions. If these modes activate during the upgrade process the upgrade may 
corrupt. 

2.

 

Make sure there is no current alarms or faults on the LCD display of Pulsar MX FRAME. If 
there are any alarms/faults present they must be cleared/solved before running the 
upgrade. 

 

 

 

For example, the LCD display should show a message like below with no faults on line 3: 

 

  L O A D    P R O T E C T E D       

   

  x  .  x k V A / x x x % L O A D E D 

   

  O N L  I  N E    MO D E             

   

  S  I  N G L E    U P S               

   

 
 

 

 

Below an example of a displayed internal fault that has to be solved before starting the firmware 
upgrade: 

 

  L O A D    P R O T E C T E D           
  x  .  x k V A / x x x % L O A D E D     

  I  N T E R N A L    F A U L T           

  S  I  N G L E    U P S                   

 
 

 

 

Содержание MGE Pulsar MX Frame

Страница 1: ...these modes activate during the upgrade process the upgrade may corrupt 2 Make sure there is no current alarms or faults on the LCD display of Pulsar MX FRAME If there are any alarms faults present t...

Страница 2: ...tion See below 1 The LED s will show automatic bypass as indicated 2 Unlock the Manual Bypass switch and set to the TEST position Step 3 Unzip the file Pulsar MX Upgradev35b09242008 zip sent by suppor...

Страница 3: ...lsar MX Upgradev33b09242008 exe Depending on the requirement select the components that you have to upgrade by selecting deselecting them with the tick boxes For example to upgrade the Frame only dese...

Страница 4: ...4008030 AD Page 4 Press the Upgrade Now button to automatically launch the upgrade of the soft After detection of the UPS the programming will start automatically Pulsar MX 4000 5000 RT Pulsar MX Fram...

Страница 5: ...nt panel and select the following Select maintenance Model Power modules Frame and check that the version are correct for both the System and power modules Pulsar MX FRAME For the Frame we are V01H an...

Страница 6: ...oid re flashing the frame unnecessarily and launch the upgrade again but this time just for the power modules If the Frame do not show the correct version then re run the upgrade from step 4 but desel...

Страница 7: ...art the inverter See below 1 Make sure the UPS indicates Automatic bypass as indicated 2 Turn the Bypass switch from TEST to NORMAL 3 Start the Inverter by pressing the 1 for more than 3 seconds 4 The...

Страница 8: ...ure there is no other software like PSP that is using the serial port Close the software window with X in taskbar Restart from step 4 and launch the upgrade again IMPORTANT NOTE If during re launching...

Страница 9: ...mode Close the software window with X in taskbar Restart from step 4 and launch the upgrade again IMPORTANT NOTE If during re launching the upgrade program a program windows appears with message Do y...

Страница 10: ...ware window with X in taskbar Restart from step 4 and launch the upgrade again IMPORTANT NOTE If during re launching the upgrade program a program windows appears with message Do you want to continue...

Страница 11: ...wer Modules s fan should be off Restart computer Take care on PSP software auto launch if yes Stop PSP Turn the Bypass switch from BYPASS to TEST Re Insert Battery module 1 1st floor Turn on external...

Страница 12: ...ware window with X in taskbar Restart from step 4 and launch the upgrade again IMPORTANT NOTE If during re launching the upgrade program a program windows appears with message Do you want to continue...

Отзывы: