Eaton 93PM-L 20–200kW (208V) UPS Installation and Operation Manual 164000724—Rev 01
23
Table 5. Input/Output Ratings and Wiring Recommendations: 10– 50 kW (208/208)
Basic Unit Rating
Units
Rating 50/60 Hz
kW
10
20
30
40
50
Input and Output Voltage
Volts
208/208
208/208
208/208
208/208
208/208
AC Input to UPS Rectifier (0.99
Minimum pF)
Full load current plus battery recharge
current
(3) Phases, (1) Ground
A
Amps
36
71
107
142
178
Minimum Conductor Size (Phase A, B,
and C)
Number per Phase
AWG or
kcmil
(each)
6
(1)
2
(1)
2/0
(1)
4/0
(1)
250 MCM
(1)
Minimum Conductor Size (Ground)
Number
–
AWG or
kcmil
(each)
8
(1)
8
(1)
4
(1)
2
(1)
2
(1)
AC Input to UPS Bypass (Four Wire,
Dual-Feed)
Full Load Current (3) Phases – see Note,
(1) Ground
B
Amps
36
71
107
142
178
Neutral Current
Amps
48
96
144
192
240
Minimum Conductor Size (Phase A, B,
and C)
Number per Phase
AWG or
kcmil
(each)
6
(1)
1
(1)
3/0
(1)
250 MCM
(1)
400 MCM
(1)
Neutral Wire Size
Number
AWG or
kcmil
(each)
3
(1)
2/0
(1)
300 MCM
(1)
500 MCM
(1)
4/0
(2)
Minimum Conductor Size (Ground)
Number
–
AWG or
kcmil
(each)
8
(1)
6
(1)
4
(1)
2
(1)
1/0
(1)
DC Input from External Battery (Line-Up-and-Match Eaton 93PM-L IBC-SW, IBC-LW or IBC-LHW)
For Line-Up-and-Match wiring refer to
Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded
or
Eaton 93PM
Universal Integrated Battery Cabinet Installation Manual-Large and Large High Rate
DC Input from External Battery
(Standalone Eaton 93PM-L IBC)
(1) Positive, (1) Negative, (1) Ground
C
Total
Amps
23
45
68
90
113
Minimum Conductor Size (Phase Positive
and Negative)
Number per Pole
AWG or
kcmil
(each)
10
(1)
6
(1)
4
(1)
2
(1)
1
(1)
Minimum Conductor Size (Ground)
Number
–
AWG or
kcmil
(each)
8
(1)
8
(1)
8
(1)
8
(1)
6
(1)
Содержание 93PM-L IAC-B
Страница 1: ...p n 164000724 Revision 01 20 200 kW 208V UPS Installation and Operation Manual Eaton 93PM L UPS ...
Страница 10: ...x Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 List of Tables ...
Страница 112: ...102 Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 UPS System Installation ...
Страница 148: ...138 Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 Communication ...
Страница 154: ...144 Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 UPS Maintenance ...
Страница 158: ...148 Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 Product Specifications ...
Страница 161: ...Eaton 93PM L 20 200kW 208V UPS Installation and Operation Manual 164000724 Rev 01 151 Warranty ...
Страница 162: ...16400072401 164000724 01 ...