CLINK II SCU MANAGER
electric circuit diagrams scu
version 5.0
80
Figure 30: Auxiliary circuit Forward / Reverse starter
Note
•
The main circuit contains fuse F1, isolator Q1 and contactors K1, K2. To be able to determine the status
(OFF, LEFT, RIGHT) of the main circuit, the status of K1 (figure 30) and K2 is read in by the Starter Control
Unit through the digital inputs DI_1 and DI_2. The status of the isolator is read in through digital input
DI_0. Digital inputs are used for manual control (S10, S11 and S12). The auxiliary relays K10, K11 and
K12 are activated with the outputs DO_0, DO_1 and DO_2.
•
Direct switch off via auxiliary circuit is possible with S1.
F2
OFF
K12
K11
K1
K1
LEFT
S1
K2
K2
RIGHT
K1
K12
K2
K11
K10
K10
OFF
K11
LEFT
K12
RIGHT
Q1
DI_1
DI_2
DI_3
DI_4
DI_5
DI_6
DI_7
DO_0
DO_1
DO_2
DO_3
DO_4
DO_5
DO_6
DO_7
V+_Tray
DI_0
K1
K2
S10
S11
S12