CLINK II SCU MANAGER
functional description scu
version 5.0
54
5.8.13
Under Current Protection
The purpose of this protection is to monitor the minimum value of the motor current.
Trip and warning levels are set as a percentage of the nominal motor current.
5.9
Monitoring of diagnostic and maintenance data
The diagnostic and maintenance data are described in this paragraph.
5.9.1
Number of operating hours
Number of operating hours is understood to mean the cumulative time that one of the contactors K1 or K2 was
activated. The resolution with which the number of running hours is displayed is 0.1 hour. Internally a much
smaller resolution (100 ms) is used, so that a motor that was 6 times 1 minute in status RUNNING, also
increases the number of running hours by 0.1.
The number of running hours is represented via LCU-5 (select
SCU Manager - Module Maintenance
) and is
available to the process controller. See table 45.
The Number of Operating Hours can be reset via LCU-5.
Select:
SCU Manager - Module Maintenance
.
Under Voltage Trip Level
0-100
0
%
Setpoint
Under Voltage Trip Time
0-100
10
s
Setpoint
Under Voltage Interlock Time
0-100
5
s
Setpoint
Table 44: Under Current Setpoints
Name
Range
Default
Unit
Parameter
type
Under Current Warning Level
0-100
0
%
Setpoint
Under Current Trip Level
0-100
0
%
Setpoint
Under CurrentTrip Time
0-100
10
s
Setpoint
Under Current Interlock Time
0-100
5
s
Setpoint
Table 45: Number of Operating Hours
Name
Range
Unit
Parameter type
Number of Operating Hours
0-4,000,000
hours
Actual
Table 43: Under
Voltage
Setpoints
Name
Range
Default
Unit
Parameter
type