CLINK II SCU MANAGER
maintenance scu
version 5.0
67
•
Replace the interface board.
•
Mount the side plates of the cassette.
•
Place the main board back in the cassette.
3
Commission the node of the new interface board via RSNetWorx™, see Use of Hyper Terminal in 7.3 on
page 67 (the default node of a new interface board is 63).
4
Download the saved settings from file to device. Select
LCU-5 System Manager - Unit Download.
5
Verify whether the main board is operational (Module LED should light solid green, see also 6.2 on page
58).
7.3
Use of Hyper Terminal
The program Hyper Terminal can be used as a practical tool for commissioning and maintenance of the Clink
II units. In the embedded software of the SCU a monitor program is included. The Hyper Terminal can be used
to communicate with this monitor program.
Warning
The Hyper Terminal may only be used by authorized personnel. Via Hyper Terminal direct access to
the embedded software is possible. Changes made to the software may result is malfunctioning of
the Clink II system at the risk of e.g. stopping or starting motors or in changing of the protection
parameters.
To connect the PC with Hyper Terminal to the Clink II unit a so called Reset box (Holec part number 1307 223)
is necessary.
To communicate via Hyper Terminal the settings of the serial port of the PC are:
bits per second: :9600
databits: 8
parity: none
stopbits: 1
datatransport: none
Under
Properties
the emulation type should be auto detection.
With the command < h > an overview of the available commands can be seen.
To assign a new node number to a Starter Control Unit, type < MAC xx >, where xx is the node number.
To adjust the baud rate on DeviceNet level to 500 kBaud type < MAC 500 >.
To give a reset command type 0, use the command RST. All data present in the RAM memory on the main
board is written in the EEPROM on the interface board.