CLINK II SCU MANAGER
functional description scu
version 5.0
53
5.8.10
External protection
The Starter Control Unit has 8 digital inputs. The five free inputs (DI_3 to DI_7) can be used for the connection
of an external protection unit to switch the motor off when the unit responds or to generate only a warning.
Configuration digital inputs
For information regarding the configuration of Digital Input Functions see 5.3.1 on page 25.
The output of the protection unit must have a potential-free contact with the following specifications:
•
Insulation: 2.5 kV/50Hz/1 min. (between contact and other parts of the unit)
•
switching power: must be suitable for switching 10 mA at 24 Vdc.
Connections
The potential-free contact of a protection unit is connected between the +24V and the respective digital input
of the Starter Control Unit.
The input signal will only be effective when the input concerned has been configured as an External Protection
function and when the respective protection procedure has been activated.
Activation of the protective device
Activation of the protective device is possible via LCU-5.
When the protection unit responds, the motor will be switched off after 0.1 second if the trip function is enabled.
When the warning function is enabled there will only be a warning after 0.1 second.
5.8.11
Over Voltage Protection
The purpose of this protection is to monitor the maximum voltage limit.
Trip and warning levels are set as a percentage of the nominal mains voltage.
5.8.12
Under Voltage Protection
The purpose of this protection is to monitor the minimum voltage limit.
Trip and warning levels are set as a percentage of the nominal mains voltage.
Table 42: Over
Voltage
Setpoints
Name
Range
Default
Unit
Parameter
type
Over Voltage Warning Level
0-130
130
%
Setpoint
Over Voltage Trip Level
0-130
130
%
Setpoint
Over Voltage Trip Time
0-100
10
s
Setpoint
Over Voltage Interlock Time
0-100
5
s
Setpoint
Table 43: Under
Voltage
Setpoints
Name
Range
Default
Unit
Parameter
type
Under Voltage Warning Level
0-100
0
%
Setpoint