CLINK II SCU MANAGER
functional description scu
version 5.0
56
The measured value for Starting Kx Current is refreshed each time Motor Starting Kx changes from TRUE to
FALSE.
5.9.5
Starting time
The Starting Kx Time is the time during which Motor Starting Kx is TRUE with a minimum of 200 ms because
of the inrush current. See also 5.6.3 on page 33.
Starting Time can be read-out via LCU-5. See table 49. Select:
SCU Manager - Module Maintenance
.
The measured value for Starting Kx Time is refreshed each time Motor Starting Kx changes from TRUE to
FALSE.
5.9.6
Trip current L1, L2, L3
The trip current Lx is the measured value for motor current Lx at the moment when the Trip Status changes
from FALSE to TRUE.
The trip current can be read-out related to In and in Ampere via LCU-5. See table 50. Select
SCU Manager -
Module Maintenance
Trip current is refreshed each time a protection function is called.
Starting K2 Current
0-1,200.000
A
Actual
Table 49: Read-out of Starting Time
Name
Range
Unit
Parameter
type
Starting K1 Time
0-100.00
s
Setpoint
Starting K2 Time
0-100.00
s
Setpoint
Table 50: Read-out of Trip Current
Name
Range
Unit
Access
Rule
Trip Current L1
0-10.00
I/In
Actual
Trip Current L2
0-10.00
I/In
Actual
Trip Current L3
0-10.00
I/In
Actual
Trip Current L1
0-1,200.000
A
Actual
Trip Current L2
0-1,200.000
A
Actual
Trip Current L3
0-1,200.000
A
Actual
Table 48: Read-out of Starting Current
Name
Range
Unit
Parameter
type