CLINK II SCU MANAGER
functional description scu
version 5.0
33
5.6.3
Starting
An engine is starting when the motor reaches a certain status (ON, STAR, DELTA, LEFT, RIGHT, LOW, HIGH)
and one of the following conditions has not yet been met:
•
The motor current has dropped below the change-over current level
•
The change-over time has elapsed
In figure 7 the motor reaches a certain status at the moment t0. The motor current increases and will decrease
after some time to, for instance, the nominal motor current. As soon as the motor current drops below the
change-over current level, starting has finished.
In figure 8, contrary to figure 7, the end of the starting is determined by the change-over time.
Figure 7: Determining starting by Change Over Current Level
Change Over Time
t0
off
starting
running
Nominal Motor Current
Change Over Current level
mot
o
r c
u
rrent
t