CLINK II SCU MANAGER
functional description scu
version 5.0
38
MOTOR STOPPED TO MOTOR RUNNING 2
See figure 13, left:
•
After a start2 command, K11 is energized causing K1 and ContactorK3 to energize.
•
When MotorStartingK1 has finished, K11 and K12 are energized simultaneously, causing K1 to de-ener-
gize.
•
When the Interlock2Time has elapsed, K12 is energized causing K2 to energize.
•
When Motor Starting 2 has finished, the end status is reached (Motor Running 2).
MOTOR RUNNING 2 TO MOTOR STOPPED
See figure 13, right:
•
After a stop command, K10 is energized causing K2 and K3 to de-energize.
Figure 14: Time diagrams Motor Stopped to Motor Running 1 and Motor Running 1 to Motor Stopped
MOTOR STOPPED TO MOTOR RUNNING 1
See figure 14, left:
•
After a start1 command, K11 is energized causing K1 and K3 to energize.
•
When motor starting1 has finished, the end status is reached.
MOTOR RUNNING 1 TO MOTOR STOPPED
See figure 14, right:
•
After a stop command K10 is energized causing K1 and K3 to de-energize.
AuxiliaryRelayK10
AuxiliaryRelayK11
ContactorK1
AuxiliaryRelayK12
ContactorK2
ContactorK3
MotorStopped
MotorStarting1
MotorRunning1
Start1
Stop
MotorRunning1
MotorStopped
MotorStartingK1