![Eaton Holec Clink II Скачать руководство пользователя страница 45](http://html1.mh-extra.com/html/eaton-holec/clink-ii/clink-ii_user-manual_3683038045.webp)
CLINK II SCU MANAGER
functional description scu
version 5.0
45
•
Under voltage protection: see 5.8.12 on page 53
•
Under current protection: see 5.8.13 on page 54
5.8.1
Characteristics of protection functions
•
Each protection function has an input for a variable to be observed and inputs for setpoints which are set
via LCU-5 by selecting:
SCU Manager - Module Protection - Settings
.
•
After having been configured, each protection function is performed autonomously by the Starter Control
Unit.
•
Each protection function has the facility to generate a trip signal to switch off the motor in the event that
one of the setpoints is exceeded.
•
Each protection function (except motor stall) has the facility to generate a warning signal in the event that
one of the setpoints is exceeded.
•
Setpoints are used to define which trip and warning signals can be acknowledged via manual control or
process control.
The status of a protection function can be read-out via LCU-5, by the process controller and on the motor starter
tray.
Protection states:
•
Fault not present.
•
Protection activated, message not yet confirmed by an acknowledge/reset command.
•
Message acknowledged but fault is still present.
5.8.2
Read-out of trip and warning signals
Via LCU-5 and the process controller the following statuses can be read-out (see also table 31):
•
Trip Status indicates which protection has been activated.
•
Trip Acknowledge Status indicates which protection has been activated and also has been confirmed by
means of an acknowledge command.
•
Warning Status indicates which protection gives a warning signal.
•
Warning Acknowledge Status indicates which protection gives a warning signal and also has been con-
firmed by means of an acknowledge command.
Table 31: Read-out of protection status registers
Name
Description
Parameter
type
Trip Status
Motor stall
Motor Overload
Phase Unbalance
Earth Leakage
Process Overload
Process Underload
External Protection
Over Voltage Protection
Under Voltage Protection
Under Current Protection
Actual
Trip Acknowledge Status
See description Trip Status
(above)
Actual