CLINK II SCU MANAGER
functional description scu
version 5.0
21
Read-out of the motor temperature
Model parameters
The model parameters are calculated by the SCU on the basis of the motor data. For the calculation, use is
made of the name-plate data of the motor which have to be entered via LCU-5. Select:
SCU Manager - Module
Protection - Settings - tab Motor
. For lacking data, standard values are entered. An overview of the data to be
entered as well as a short explanation is given via LCU-5. Select:
SCU Manager - Module Protection - Settings -
tab Motor
, (see table 12).
While entering the parameters, the ranges are checked by LCU-5. The mutual ratios are checked by the SCU.
In case of an invalid value a major recoverable fault will be generated. See Fault messages‚ page 61 for a
description.
Table 11: Motor temperature parameters
Name
Range
Unit
Parameter
type
Motor Temperature Cu
0-190.0
K
Actual
Motor Temperature Fe
0-190.0
K
Actual
Table 12: Motor data parameters
Name
Range
Unit
Parameter
type
Motor Weight
2-6,000
kg
Setpoint
Stall Current1
2.50-10.00
I/In
Setpoint
Stall Current2
2.50-10.00
I/In
Setpoint
Stall Time 1
2.0-30.0
s
Setpoint
Stall Time 2
2.0-30.0
s
Setpoint
Stall Time Condition
Cold
Hot
-
Setpoint
Overload Current
0.80-1.15
I/In
Setpoint
Trip Time At 1.5 In
4-720
s
Setpoint
Maximum Temperature Rise
50-125
K
Setpoint
Warning Temperature Rise
0-125
K
Setpoint
Temperature Rise Interlock
Level
0-130
K
Setpoint
Cooling ratio
1.0-20.0
-
Setpoint
Nominal Voltage
220-690
V
Setpoint
Auxiliary CT ratio
1-1,200
-
Setpoint
Nominal Power 1
0.09-600.00
kW
Setpoint
Nominal Power 2
0.09-600.00
kW
Setpoint