CLINK II SCU MANAGER
functional description scu
version 5.0
55
5.9.2
Number of contactor operations
Number of contactor operations is understood as the number of times a contactor is switched from off to on.
The number of contactor operations is represented via LCU-5 (select
SCU Manager - Module Maintenance
) and
is available to the process controller. See table 46.
The Number of Contactor Operations can be reset via LCU-5 by selecting:
SCU Manager - Module Maintenance
- Reset - reset Number of Starts
.
5.9.3
Number of contactor operations during last hour
Number of contactor operations during last hour is understood to mean the number of times a contactor was
switched from off to on during the last hour.
The number of contactor operations is represented via LCU-5 (select:
SCU Manager - Module Maintenance
) and
is available to the process controller. See table 47.
It is not possible to reset The Number of Contactor Operations Last Hour.
5.9.4
Starting current
The Starting Kx Current is the maximum motor current measured during the period Motor Starting Kx is TRUE
(5.6.3 on page 33) starting after 200 ms because of the inrush current.
The Starting Current is represented both related to ‘In’ and in ampere via LCU-5, see table 48. Select:
SCU
Manager - Module Maintenance
.
Table 46: Read-out of Number of Contactor Operations
Name
Range
Unit
Parameter
type
Number of Contactor K1 Operations
0-4,000,000
-
Actual
Number of Contactor K2 Operations
0-4,000,000
-
Actual
Table 47: Read-out of Number of Contactor Operations Last Hour
Name
Range
Unit
Parameter
type
Number of Contactor K1 Operations
Last Hour
0 - 64
-
Actual
Number of Contactor K2 Operations
Last Hour
0 - 64
-
Actual
Table 48: Read-out of Starting Current
Name
Range
Unit
Parameter
type
Starting K1 Current
0-10.00
I/In
Actual
Starting K2 Current
0-10.00
I/In
Actual
Starting K1 Current
0-1,200.000
A
Actual