U Page 48
Digital controller RK 4004
.9.4. auto address
The controller card features automatic sensor addressing.
Sensor addressing is only performed after a reset and is only pos-
sible for sensors that are directly connected to the controller card
at connectors X 5/X 6. Furthermore, the sensors must feature the
appropriate software for automatic sensor addressing.
The following sensor addressing options are possible.
0 =
The sensor address/es is/are only displayed in parameters
"connector X5" and "connector X6". The address is manually
set on the sensor or via the command device.
1 =
Device number 1 is automatically assigned to the sensor at ter-
minal X5 and device number 2 to the sensor at terminal X6. The
sensor device group is identical with the controller card group.
Address setting according to the sensor description is thus un-
necessary.
2 =
The sensor at terminal X5 (X6) is assigned the address set in
the "connector X5" ("connector X6) parameter. In the event of
sensor replacement (defective sensor) the new sensor is auto-
matically assigned the right address.
.9.5. CAN connector Right
.9.6. CAN connector Left
The address setting of the sensor at terminal X5 (X6) is displayed.
.9.7. >function config 1
Certain functions may be activated or deactivated.
The following table indicates the possible functions: