62
VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Tap/softened water:
MAINTENANCE
WARNING
Electric shock hazard
Contact with energized circuits can
cause severe personal injury or
death as a result of electric shock. To
prevent shock, disconnect electrical
power before performing service or
maintenance procedures on an part of
the humidifi cation system.
When performing maintenance on the
humidifi er:
• Always switch the keypad control
mode to Standby.
• Place all power disconnects in OFF
position and lock in OFF position.
• Close the fi eld-installed manual
supply water shut-off valve.
mc_031110_0444
WARNING
Hot surface and hot water hazard
Do not touch the tank or drain piping
until the unit has had suffi cient time to
cool, or serious injury can occur.
Opening the drain valve when the
tank is hot can discharge water with a
temperature up to 212 °F (100 °C) into
the plumbing system. This can cause
damage to the plumbing system if the
humidifi er is not properly connected
to a water tempering device such
as a DriSteem Drane-kooler
™
water
tempering device.
mc_060110_1640
The best way to determine how often your humidifi er needs maintenance is to
remove the tank cover and inspect it for mineral deposits after three months
of duty. Hours of operation and duty cycle will determine your maintenance
schedule, as will water quality.
Water quality
Maintenance requirements vary with water quality, because tap and softened
water carry a variety of minerals and other materials in a mix that varies from
location to location. Very hard (high mineral content) water requires more
frequent cleaning and drain/fl ush cycles than water with low mineral content.
Softened water signifi cantly reduces mineral accumulation inside the humidifi er.
Note: Solids, like silica, are not removed in the softening process.
Skim duration
Skim duration determines the quantity of water skimmed with each fi ll cycle
and is fi eld adjustable using the Vapor-logic keypad/display.
Skimming reduces the need for frequent humidifi er cleaning. Each time the
tank refi lls, it fi lls to a level just above the lip of the skim/overfl ow fi tting. A
portion of the fi ll water fl ows out of the skim/overfl ow fi tting to the drain, which
fl ushes minerals left by the previous evaporating cycle and skims away surface
residue.
Both humidifi er cleaning and heated water fl owing to the drain are operational
costs. DriSteem recommends that the user observe and adjust the skim duration
to achieve a balance between reducing mineral buildup and conserving
heated water.
mc_060210_1430
Water quality and skim duration