19
VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Outdoor Enclosure:
• Outdoor Enclosure must be level and located so there is enough clearance
for opening access doors.
• Verify that position of support legs, pad, or curb properly support unit, and
support structure dimensions coincide with unit dimensions.
• Locate unit so air intakes are not too close to exhaust fan outlets, gasoline
storage, or other contaminants that could cause dangerous situations.
Using and storing gasoline or other fl ammable vapors and liquids in open
containers in the vicinity of this appliance is hazardous.
• When located on roof, Outdoor Enclosure air intakes must be a minimum
of 14" (356 mm) above roof to prevent intake of snow or splashed rain.
Locate Outdoor Enclosure so prevailing winds do not blow into air intakes.
• Remove all shipping brackets and other packaging prior to installing
Outdoor Enclosure.
• During transit, unloading, and setting of unit, bolts and nuts may have
become loosened. Check that all nuts are tightened.
• There are four knockouts on the right and left side of the enclosure. It is
recommended that electrical power is run into enclosure at these knockouts.
• Outdoor Enclosure is designed for lifting by two methods:
– Preferred method of lifting is by forklift. This is only possible if the forks
extend across entire unit. Forks that do not extend across entire unit
could cause tipping, resulting in unsafe conditions or damage to the
unit.
– Alternative method of lifting is through unit’s channel base frame and/
or special lifting lug hooks installed on the unit. Use a load spreader of
suffi cient width to ensure that lifting cables clear sides of unit. If such a
spreader is not available, insert wood strips between cables and unit
where necessary. All four lifting points must be used; they are marked
“lift here” on the unit.
In both cases it must be lifted from the bottom base and kept level, and
it must not tip, fall, or twist. If unit is severely twisted during handling,
permanent damage could occur. It is installer’s responsibility to verify
handling equipment’s capability to safely handle Outdoor Enclosure.
DC-1110
Flush
14" (356 mm)
OM-1095
Curb
INSTALLATION
FIGURE 19-1: OUTDOOR ENCLOSURE
MOUNTING OPTIONS
Mounting