59
VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Table 59-1:
Area-type (evaporative steam) minimum distances for rise, spread, and throw*
Maximum steam
capacity
60 °F (16 °C)
30% RH
40% RH
50% RH
Rise
Spread
Throw
Rise
Spread
Throw
Rise
Spread
Throw
lbs/hr
kg/h
ft
m
ft
m
ft
m
ft
m
ft
m
ft
m
ft
m
ft
m
ft
m
50
20
1.0
0.3
2.0
0.6
6.0
1.8
1.0
0.3
2.0
0.6
6.0
1.8
1.0
0.3
2.5
0.8
6.0
1.8
75
34
3.0
0.9
3.0
0.9
8.0
2.4
3.0
0.9
3.0
0.9
8.0
2.4
3.0
0.9
4.0
1.2
8.0
2.4
100
45
4.0
1.2
4.0
1.2
10.0
3.1
4.0
1.2
4.0
1.2
10.0
3.1
4.0
1.2
5.0
1.5
10.0
3.1
150
68
6.0
1.8
5.0
1.5
12.0
3.7
6.0
1.8
5.0
1.5
12.0
3.7
6.0
1.8
5.0
1.5
12.0
3.7
200
90
7.0
2.1
7.0
2.1
13.0
4.0
8.0
2.4
7.0
2.1
14.0
4.3
8.0
2.4
7.0
2.1
14.0
4.3
225
102
7.0
2.1
7.0
2.1
13.0
4.0
8.0
2.4
7.0
2.1
14.0
4.3
8.0
2.4
7.0
2.1
14.0
4.3
250
110
8.0
2.4
8.0
2.4
15.0
4.6
9.0
2.7
9.0
2.7
16.0
4.9
9.0
2.7
9.0
2.7
16.0
4.9
285
130
9.0
2.7
9.0
2.7
17.0
5.2
10.0
3.1
10.0
3.1
18.0
5.5
10.0
3.1
10.0
3.1
18.0
5.5
Maximum steam
capacity
70 °F (21 °C)
30% RH
40% RH
50% RH
Rise
Spread
Throw
Rise
Spread
Throw
Rise
Spread
Throw
lbs/hr
kg/h
ft
m
ft
m
ft
m
ft
m
ft
m
ft
m
ft
m
ft
m
ft
m
50
20
1.0
0.3
1.5
0.5
4.0
1.2
1.0
0.3
2.0
0.6
4.0
1.2
1.0
0.3
2.0
0.6
4.0
1.2
75
34
2.0
0.6
2.0
0.6
6.0
1.8
2.0
0.6
2.5
0.8
6.0
1.8
2.0
0.6
2.5
0.8
6.0
1.8
100
45
3.0
0.9
3.0
0.9
8.0
2.4
3.0
0.9
3.0
0.9
8.0
2.4
3.0
0.9
3.0
0.9
8.0
2.4
150
68
4.0
1.2
4.0
1.2
10.0
3.1
4.0
1.2
4.0
1.2
11.0
3.4
4.0
1.2
4.0
1.2
11.0
3.4
200
90
5.0
1.5
5.0
1.5
11.0
3.4
5.0
1.5
5.0
1.5
12.0
3.7
5.0
1.5
5.0
1.5
12.0
3.7
225
102
5.0
1.5
5.0
1.5
11.0
3.4
5.0
1.5
5.0
1.5
12.0
3.7
5.0
1.5
5.0
1.5
12.0
3.7
250
110
6.0
1.8
6.0
1.8
12.0
3.7
6.0
1.8
6.0
1.8
13.0
4.0
6.0
1.8
6.0
1.8
14.0
4.3
285
130
7.0
2.1
7.0
2.1
14.0
4.3
7.0
2.1
7.0
2.1
15.0
4.6
7.0
2.1
7.0
2.1
16.0
4.9
* With fan on high speed
mc_030210_0940
VLC-OM-020
Table 59-2:
Area-type electric fan specifications*
Motor
120 V, 50/60 Hz
Blade diameter
18" (457 mm)
Speeds
3
Control
Rotary switch
cfm (high speed)
3190
m
3
/s (high speed)
1.51
rpm (high speed)
1500
Amps (high speed)
1.52
Rise
Spread
Throw
Spread: Minimum non-wetting
width from the steam
chute
Rise:
Minimum non-wetting
height above the
steam chute
Throw:
Minimum non-wetting
horizontal distance
from the steam chute
Area-type fan
INSTALLATION
Dispersion:
FIGURE 59-1: AREA-TYPE RISE, SPREAD, THROW