8
VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Weights and cabinet sizes
Table 8-1:
Vaporstream weights and control cabinet sizes, tap/softened water and RO/DI water
Vaporstream
model
(kW-stages)
Shipping
weight
Operating
weight
†
Control cabinet size*
(M, L, XL, XXL)
Single-phase power
Three-phase power
lbs
kg
lbs
kg
120V
208V
240V
277V
480V
600V
208V
240V
277V
480V
600V
2-1
35
16
79
36
M
M
M
M
M
M
—
—
—
—
—
3-1
35
16
79
36
M
M
M
M
M
M
—
—
—
—
—
4-1
35
16
79
36
M
M
M
M
M
M
—
—
—
—
—
5-1
35
16
79
36
M
M
M
M
M
M
—
—
—
—
—
6-1
57
26
157
71
—
M
M
M
M
M
M
M
M
M
M
9-1
57
26
157
71
—
M
M
M
M
M
M
M
M
M
M
12-1
57
26
157
71
—
—
—
M
M
M
M
M
M
M
M
16-1
57
26
157
71
—
—
—
—
M
M
M
M
M
M
M
21-1
57
26
157
71
—
—
—
—
M
M
—
—
M
M
M
25-1
57
26
157
71
—
—
—
—
—
M
—
—
—
M
M
12-2
79
36
237
108
—
L
L
L
L
L
L
L
L
L
L
18-2
79
36
237
108
—
L
L
L
L
L
L
L
L
L
L
24-2
79
36
237
108
—
—
—
L
L
L
L
L
L
L
L
32-2
79
36
237
108
—
—
—
—
L
L
L
L
L
L
L
42-2
79
36
237
108
—
—
—
—
L
L
—
—
L
L
L
50-2
79
36
237
108
—
—
—
—
—
L
—
—
—
L
L
18-3
110
50
326
148
—
L
L
L
L
L
L
L
L
L
L
27-3
110
50
326
148
—
XL
L
L
L
L
L
L
L
L
L
36-3
110
50
326
148
—
—
—
XL
L
L
L
L
L
L
L
48-3
110
50
326
148
—
—
—
—
L
XXL
XL
L
L
L
L
63-3
110
50
326
148
—
—
—
—
XL
XXL
—
—
L
L
L
75-3
110
50
326
148
—
—
—
—
—
XXL
—
—
—
L
XXL
24-4
153
70
427
194
—
L
L
L
L
L
L
L
L
L
L
36-4
153
70
427
194
—
XL
XL
XL
L
L
L
L
L
L
L
48-4
153
70
427
194
—
—
—
XL
L
L
XL
L
L
L
L
64-4
153
70
427
194
—
—
—
—
XL
XXL
XL
XL
XL
L
L
84-4
153
70
427
194
—
—
—
—
XL
XXL
—
—
XL
L
L
100-4
153
70
427
194
—
—
—
—
—
XXL
—
—
—
L
XXL
*
Control cabinet sizes in this table are for the largest required cabinet for each model. Depending on Vaporstream options chosen you may receive
a smaller cabinet than the one shown in this table. Contact DriSteem if you need more detailed information about control cabinet sizes. See control
cabinet dimensions in Table 6-1.
†
Operating weight does not include control cabinet. See control cabinet weights in Table 6-1.
mc_021010_0446
SPECIFICATIONS