56
GTS HUMIDIFIER LX SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
START-UP CHECKLIST
After the system is installed and connected to gas, electrical, water supplies,
controls, steam dispersion, and drain check the following items:
Verify that the GTS humidifier, controls, piping, electrical connections, steam
supply, and dispersion unit(s) are installed according to the following:
• Installation instructions in this manual
•
Vapor-logic Installation and Operation Manual
(shipped with the
humidifier)
- Installation section
- Installation checklist
• Ladder style wiring diagram (shipped inside unit)
• External connections wiring diagram (shipped inside unit)
• Gas connection instructions in this manual
• Mounting instructions in this manual
• All governing codes
Piping (gas)
• Verify that the gas type supplied to the humidifier matches the unit
nameplate label.
• Verify that all field and humidifier gas piping has been tested for leaks.
(Soap and water are not recommended near gas valves.)
Piping (steam, drain, supply water)
—Verify that all piping connections have
been completed as recommended and that water pressure is available.
Electrical
—Verify that all wiring connections have been made in accordance
with all governing codes and the GTS wiring diagrams.
Controls
—Verify that all control wiring has been completed as specified and
required for correct and safe operation of the GTS humidifier. Refer to the
Vapor-logic Installation and Operation Manual.
Verify that the humidifier tank is securely installed and level before filling
with water (see the operating weights in Table 11-1.
Verify that the humidifier tank is level front to back and side to side after it is
full of water.
Start-up
The
Vapor-logic Installation and Operation
Manual
is a comprehensive operation manual.
Refer to it for information regarding the
following features:
• Display setup and menu information
• Control input signals and functions
• Drain, flush, and skim features
• Safety features
• Alert screens and fault messages
The manual was shipped with your humidifier.
Additional copies can be viewed, printed, or
ordered on our website: www.dristeem.com
OPERATION
WARNING
Startup
Only qualified electrical and gas
personnel should perform the start-up
procedure.