81
GTS HUMIDIFIER LX SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
European models only
EUROPEAN MODELS
Table 81-1:
Specifications for European models
Model GTS
LX Series
Average flue
temperature
Maximum
flue back pressure
Mass flow rate of
combustion products
Minimum mass flow
rate of
combustion products
LX-50
50 °C
1.2 mbar
5.9 g/s
1.2 g/s
LX-75
50 °C
1.2 mbar
8.9 g/s
1.8 g/s
LX-100
50 °C
1.2 mbar
11.8 g/s
2.4 g/s
LX-150
50 °C
1.2 mbar
17.8 g/s
3.6 g/s
LX-200
50 °C
1.2 mbar
23.7 g/s
3.6 g/s
LX-250
50 °C
1.2 mbar
29.6 g/s
3.6 g/s
LX-300
50 °C
1.2 mbar
35.0 g/s
3.6 g/s
LX-400
50 °C
1.2 mbar
47.4 g/s
3.6 g/s
LX-500
50 °C
1.2 mbar
59.2 g/s
3.6 g/s
LX-600
50 °C
1.2 mbar
69.9 g/s
3.6 g/s
Table 81-2:
GTS models, capacities, electrical specifications, and weights, European models
GTS
model
Steam
capacity per
hour in kg*
P = (kW)
Q = (kW)
Steam outlet
Recommended flue size
Operating
weight in kg
Shipping
weight in kg
Full load
amps
LX-50
23
0-17
0-18
DN50 (2") hose/BSP
DN50 or 80 (2" or 3")
217
164
1.5
LX-75
34
0-25
0-27
DN50 (2") hose/BSP
DN80 (3")
217
164
1.5
LX-100
45
0-33
0-36
DN50 (2") hose/BSP
DN80 (3")
216
166
1.5
LX-150
68
0-50
0-54
DN50 (2") hose/BSP
DN80 (3")
285
191
2.0
LX-200
91
0-67
0-72
DN80 (3") hose/BSP/flange
DN100 (4")
415
256
2.5
LX-250
113
0-82
0-89
DN80 (3") hose/BSP/flange
DN100 (4")
415
256
2.5
LX-300
136
0-98
0-106
DN80 (3") hose/BSP/flange
DN100 (4")
415
260
2.5
LX-400
181
0-132
0-143
DN100 (4") BSP/flange
DN150 (6")
729
426
3.5
LX-500
227
0-166
0-179
DN100 (4") BSP/flange
DN150 (6")
729
426
3.5
LX-600
272
0-195
0-211
DN100 (4") BSP/flange
DN150 (6")
731
436
3.5
* Maximum steam capacities listed may be as much as 10% lower than the given values due to local variations in the Wobbe index of G20 and
G25 gases.