Product overview
WATER LEVEL CONTROL
The LX series of GTS humidifiers control water level using a three-rod probe
(see Figure 9-1). All water types and conductivities work with the universal
water system. The user does not need to select a new water type or change
hardware to change water types. Additional valves and Vapor-logic algorithms
measure and control the water level for optimum efficiency and low water
safety conditions. Vapor-logic automatically provides a steady output while
maintaining the water level between the bottom and middle probes.
Supply water
connection
Control
components
Primary heat
exchanger
Air gap
Open drain
Water level sensing probe
Secondary heat
exchanger
Overflow
outlet
OM-7943
Gas valve
Blower
Note: Dashed lines indicate supplied by installer
Water level
is controlled
electronically using
three probes
Full
Overflow/foam detection
FIGURE 9-2: GTS HUMIDIFIER LX SERIES (MODELS LX-50 THROUGH LX-150)
FIGURE 9-1: WATER LEVEL CONTROL
Flue gas vent
VLC-OM-030
Gas connection
Drain
Electrical field
connection
Flue gas condensate
Steam outlet
Combustion air pipe
Low