GTS HUMIDIFIER LX SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Notes:
• Locate air gap only in spaces with adequate temperature and air
movement to absorb flash steam; otherwise, condensation may form
on nearby surfaces. Refer to governing codes for drain pipe size and
maximum discharge water temperature.
• Dashed lines indicate provided by installer.
• Humidifier flue gases must be vented to the outside atmosphere.
• Supply water inlet is more than 2" (51 mm) above skim/overflow port,
eliminating the possibility of backflow or siphoning from tank. No
additional backflow prevention is required; however, governing codes
prevail.
• For additional backflow prevention installation, install at a minimum of
40' (12 m) from the humidifier.
• Damage caused by chloride corrosion is not covered by your DriSteem
warranty.
OM-7997
Flue gas vent
Gas inlet connection
1" (25 mm) air gap or vacuum breaker
Open drain required. See first note below.
1½" NPT (DN40) drain piping must be
rated for 212 °F (100 °C) (by installer)
Install level
Steam outlet
Steam hose or tubing
Offset humidifier from floor drain to prevent
flash steam from rising into the humidifier
Shock arrester recommended to reduce
water hammer (by installer)
Supply water line; water
pressure range 25 to 80 PSI
(172 to 582 kPa); water
Install level
INSTALLATION
Piping:
FIGURE 29-1: LX SERIES FIELD PIPING OVERVIEW - MODELS LX-200 THROUGH LX-600
Combustion air intake
Flue gas condensate
Overview
7/8" (22mm) electrical
field connection