 6050-065-C-2-16

2 Quick Guide - 1

OFF

ON

Reverse

Shadow Loop

Terminal 15 is a STANDARD Reverse input.
Terminal 15 is a Shadow input. Gate will 

NOT

 stop 

during

 the close cycle.

Switch

Function

Setting

Description

SW 2 (Bottom 8 Switches)

Secondary

Gate Opening

Direction

OFF

ON

Motor Control
for Secondary

Operator

Primary

Gate Opening

Direction

2

3

4

6

7

8

1

Switch is OFF when both primary and secondary operator motors are powered from main 
terminals 4 and 5. Applies to operators originally manufactured with 4501, Rev O boards or 
lower). 
Switch is ON when secondary operator motor is powered from the secondary motor 
terminals. Applies to operators manufactured with 4501, Rev P boards and higher, 

and all 

4502 boards. 

5

Gate Overlap

OFF

ON

OFF

ON

OFF

ON

Primary and secondary operators start at the same time.
Secondary operator starts 1-2 seconds prior to primary operator.

Same as above, for secondary 6050/6100 

ONLY

.

Monitored

Photo Sensor

Monitored

Reversing Edge

ON

OFF

Opens

Clockwise

Opens
Counter-Clockwise

When a switch setting is changed, 

power must be turned OFF and then turned back ON

 for the new setting to take affect.

QUICK GUIDE: DIP-Switches

See page 20 for descriptions about DIP-switches.

Switch

Function

Setting

Description

SW 1 (Top 8 Switches)

OFF

ON

OFF

ON

OFF

OFF

ON

1-OFF
1-OFF

1-ON
1-ON

2-OFF

2-ON

2-OFF

2-ON

Auto-Close

Timer

Not Used

Dual Operators

Single Operator

Circuit

Board

Relay

3

4

5

7

1 and 2

Auto-close timer is OFF. Manual input required to close gate.
Auto-close timer is ON. Adjustable from 1-23 seconds to close gate.
Leave in the OFF position.

OFF

ON

3-Button

Single Button

6

OFF when using a 3-button station (DoorKing 3-button control stations only).
ON when using a single button control, terminals 13 &14 become a STOP input.

Switch must be OFF when bi-parting (dual) gates are used.
Switch must be ON for single operator. 

OFF

ON

Tamper Protect

8

Tamper protect is OFF.

Normal Setting. 

Tamper protect is ON. Operator will close gate when being forced open. 

Relay activates when gate is open (Shadow loop setting when used). 
Relay activates when gate is not closed.
Relay activates when gate is opening and open. 
Relay activates when gate is opening and closing.

The output wired to terminal #12 becomes the output from the exit loop detector plugged 
into the EXIT Loop port.

Normal Setting. 

Terminal #12 is a normal full open input.

Exit Loop Port

Output

Full Open Input

Every time

 the operator is powered up, the 

First

 open command 

will

automatically set the open and close limits of the gate.

 (See page 21).

No Photo Sensor connected to Aux terminal 7 and 8.
Photo sensor is connected to Aux terminal 7 and 8 and monitored.
No Reversing edge connected to Aux terminal 9 and 10.
Reversing edge is connected to Aux terminal 9 and 10 and monitored.

OFF

Not Used

Leave in OFF position.

Содержание 6050-080

Страница 1: ...s Do not allo w chil dren to play in gate area or ope rate gate Do not stan d in gate path or wal k thro ugh path whi le gate is mov ing Rea d own er s man ual and safe ty inst ruct ions SE RI OU S IN...

Страница 2: ...ON 1 ON 2 OFF 2 ON 2 OFF 2 ON Auto Close Timer Not Used Dual Operators Single Operator Circuit Board Relay 3 4 5 7 1 and 2 Auto close timer is OFF Manual input required to close gate Auto close timer...

Страница 3: ...4 is turned OFF input will close gate When gate is closing input will reverse gate 11 This input ONLY functions when gate is fully opened or in the closing cycle When gate is closing SW 2 switch 5 is...

Страница 4: ...his manual This manual is copyrighted all rights reserved No portion of this manual may be copied reproduced translated or reduced to any electronic medium without prior written consent from DoorKing...

Страница 5: ...2 1 High Voltage Wire Runs 2 2 High Voltage Terminal Connection 2 3 Bi Parting Gates Wiring Dual Gate Operators SECTION 3 ADJUSTMENTS 18 18 19 20 21 22 22 3 1 4502 Circuit Board Description and Adjus...

Страница 6: ...o promote pedestrian usage Locate the gate such that persons will not come in contact with the vehicular gate during the entire path of travel of the vehicular gate The gate must be installed in a loc...

Страница 7: ...d and maintained serious injuries or death can result Be sure that the installer has instructed you on the proper operation of the gate and gate operator system Be sure that the installer has trained...

Страница 8: ...lar gate operator or system intended for use in a guarded industrial location or building such as an airport security area or other restricted access locations not servicing the general public in whic...

Страница 9: ...or vehicular traffic flow at entrances or exits to areas such as parking garages lots or toll areas VEHICULAR HORIZONTAL SLIDE GATE OPERATOR OR SYSTEM A vehicular gate operator or system that controls...

Страница 10: ...vehicular gate ref UL325 56 8 4 b Not Allowed OK Closed Gates Gates shall have smooth bottom edges with vertical bottom edged protrusions not exceeding 0 50 inches ASTM F2200 4 3 If distance is great...

Страница 11: ...rator s only if the gate s are at the full open position Separate Pedestrian Walkway Located so pedestrians cannot come in contact with the vehicular gate Warning Signs D Permanently mounted and easil...

Страница 12: ...through the open gate bracket intersects the operator output shaft 34 12 43 Closed Gate Open Gate Operator Output Shaft Prior to beginning the installation of the swing gate operator we suggest that y...

Страница 13: ...main gear bracket mounting holes 2 1 bolts through the main gear bracket mounting holes 2 1 bolts through the main gear bracket mounting holes Hardware for Post Mount 2 1 1 2 inch bolts For support pl...

Страница 14: ...Concrete Pad 14 10 90 DoorKing s Primary Secondary Interconnection Cable Dual Operator Application Only Secondary Operator AC Power and Communication wires Loop Lead In Wires Low Voltage wire insulat...

Страница 15: ...elease option when the crank arm is unlocked Assemble arms as shown with the gate in the closed position The elbow assembly s flange MUST be on the opposite side of the gate in the closed position Thi...

Страница 16: ...aginary straight line when open or closed Slide elbow assembly back and fourth manually opening and closing gate until arms function as shown DO NOT power up the operator to set the open and closed ga...

Страница 17: ...sensor or monitored reversing edge MUST also be installed See page 25 for AUX terminal wiring for monitored photo sensor See page 24 for MAIN terminal wiring for standard photo sensor Note A STANDARD...

Страница 18: ...iring for monitored reversing edge A monitored reversing edge Type B2 should be installed as entrapment protection for the closing cycle of the gate Typical Reversing Edge mounted on bottom of gate wh...

Страница 19: ...allation of an operator opening gates wider that 90 is the same for 1 3 through 1 8 except the operator and concrete pad will be in a different position Individual requirements can be calculated follo...

Страница 20: ...e interconnection cable that links the 2 operators together See Section 2 3 Bi Parting Gates Wiring Dual Gate operators on the next page Optional 3 3 Amp Heater Installation Note When installing the h...

Страница 21: ...h voltage and low voltage will need to be provided to the secondary operator when NOT using DoorKing s UL listed wet environment interconnection cable Red Blue White Purple Yellow Brown Orange Seconda...

Страница 22: ...1833 1835 1837 or 1838 only Auto close timer when turned ON SW 1 switch 4 ON Adjust from 1 second full counter clockwise to approximately 23 seconds full clockwise Dry relay contacts terminals 16 17...

Страница 23: ...nd closing The output wired to terminal 12 becomes the output from the exit loop detector plugged into the EXIT Loop port Normal Setting Terminal 12 is a normal full open input Exit Loop Port Output F...

Страница 24: ...ded to close gate Switch 8 Turn this switch ON when a MONITORED Reversing Edge is wired to aux terminals 9 10 Reversing Edge is active in BOTH directions of gate travel OPENING Reversing Edge Activati...

Страница 25: ...be physically adjusted The gate open and close positions are determined by the physical stop Flange on the elbow assembly See below The arms MUST already be in the correct closed configuration See Se...

Страница 26: ...lip it is too tight Repeat step 4 and re adjust the clutch Note After the gate has reversed and STOPPED the operator will be in a Soft Shutdown Press the KEY SWITCH on the circuit board to continue th...

Страница 27: ...ld timer When gate is open and auto close timer SW 1 switch 4 is turned OFF input will close gate When gate is closing input will reverse gate 11 This input ONLY functions when gate is fully opened or...

Страница 28: ...r Access Device Open Safety Open 11 Access Control Devices Com Com 24 VDC 250 ma Max Coax Antenna Kit P N 1514 073 Antenna mounted outside operator cover Important Controls intended for user activatio...

Страница 29: ...or Note Inputs are active in both directions of travel OPENING Gate Edge Activation Gate will reverse 2 inches and STOP Another input is needed to open gate CLOSING Gate Edge Activation Gate will reve...

Страница 30: ...on vehicles in the gate s path DoorKing highly recommends that loops and loop detectors be installed Loops are laid underneath cut into asphalt or concrete driveways or buried beneath gravel and earth...

Страница 31: ...hardware 7 The entrance is for vehicles only Pedestrians must use separate entrance 8 SAVE THESE INSTRUCTIONS Unlock the power switch cover and open to access the MAIN POWER and the operator RESET sw...

Страница 32: ...sed by the inherent system the gate will reverse and run back to the closed position The time clock input is still present but the gate will not re open Example 2 If the gate is closing and an entrapm...

Страница 33: ...d shutdown determine why the shutdown occurred Inspect the gate for any obstructions along its path that could have activated the inherent entrapment sensing system Inspect the gate and gate hardware...

Страница 34: ...cker reporting is in use a forced entry attempt transaction will be sent to the DoorKing access control system at this time SW 1 1 ON 2 3 4 5 6 7 8 NO AC power Manual Release In addition to FAIL SAFE...

Страница 35: ...e opening and closing cycles Adjust the clutch if necessary Check monitored safety external device s stop or reverse the gate when activated 6 1 Maintenance SECTION 6 MAINTENANCE AND TROUBLESHOOTING I...

Страница 36: ...Check any external safety devices Any short or malfunction in these devices can cause the gate operator to stop or to hold open 3 A malfunction in a loop or loop detector can cause the gate operator...

Страница 37: ...proper direction Turn power OFF and then back ON Activate a keying device Operator should run in the open direction If operator runs in the close direction turn power OFF and change direction switch...

Страница 38: ...tes and is a fail safe device allowing emergency vehicle access upon power outage P N 1216 080 and P N 1216 081 3 Button Control Station Three button interior and exterior control stations provide man...

Страница 39: ...14 13 12 11 10 9 8 7 6 5 4 3 2 1 4502 Model 6050 6100 6050 30uf Capacitor OR 6100 50uf Capacitor Reset AC Power Alarm 115 VAC NEU HOT Red Blue Blue Red White Red Yellow Brown Orange White Black Black...

Страница 40: ...p OR 6100 1 2 HP 5 4 amp Yellow Yellow Brown Orange Brown Orange Magnetic Limit Sensor 8 Gray 7 Orange 6 Brown 5 Yellow 4 Purple 3 White 2 Blue 1 Red Interconnection Cable Connection Red Red Blue Blue...

Страница 41: ...6050 065 C 2 16 37...

Страница 42: ...e Inglewood California 90301 U S A Phone 310 645 0023 Fax 310 641 1586 Series 6050 and 6100 Installation Owner s Manual Vehicular Swing Gate Operator Series 6050 and 6100 For operators manufactured Ju...

Отзывы: