Installation, Operation and Maintenance Manual
DCE 2000 Series Dust Collectors
10
General guidance to lifting
All assemblies should be lifted using the four-point lifting arrangement
(see Fig. 2).
If advantageous, the filter and fan sections may be fitted together prior to lifting
onto the base section.
Chains or slings must be used with an adequate SWL (safe working
load). (Refer to lifting label located adjacent to lifting bracket for weight
of equipment supplied by Donaldson). Chains must be long enough to
ensure that the included angle between diagonal chains is not greater
than 90°.
Ideally the chains should be adjusted to give a horizontal lift. If the chain lengths
are not adjusted the equipment will hang at an angle but can still be lifted safely.
The lifting brackets should only be used to lift the equipment as supplied.
i.e. not with any ancillary equipment fitted.
standard collectors with dust container or rotary valve
Lift the base section into position and, using plumb lines and spirit levels, line
up both horizontally and vertically using shims under legs where required.
Drill through the base section holes and insert and tighten expandible bolts (if
required, details of foundation fixing positions are provided in Publication 2325).
For collectors with dust container, locate position for dust container base panel,
drill through fixing brackets and secure with bolts. Adjust height to provide an
effective seal between dust container and sealer gear.
InstallatIon
≤
90
°
Figure 2 Four-point lifting
arrangement
Fixings located on
outside of unit
Fixings located within
clean side of unit
Figure 3 applying sealant to
base section joint flange