EN
32
DUAL CLIMA R
6.6.8
Connecting a Heat Pump auxiliary pump (C6)
The
DUAL CLIMA R
heat pump allows the connection of a circulation pump (
C6
) to increase the water
flow rate of the machine if necessary, in addition to that obtained by its internal pump (
C4
). This
C6
circulation pump will work in parallel with the internal pump of the
C4
machine only when it is operating
in the Heating or Cooling mode.
The electrical connection of the circulating pump will be made between terminals
C6L
and
N
(Neutral)
of the component terminal of the heat pump.
IMPORTANT: Before carrying out any work on the electrical installation of the heat pump,
always ensure it is disconnected from the mains.
6.6.9
Room thermostat installation
The
DUAL CLIMA R
heat pump incorporates 2 connections in the components terminal strip prepared
for the connection of up to two room chrono-thermostats or room thermostats (see
"Electrical
Diagrams"
), which will manage the heating or cooling service of the heating/cooling installation, turning
off the operation of the heat pump when the desired temperature inside home is reached and turning
on again when it descends. By means of
C-COM
input it will activate and deactivate the Cooling mode,
and by means of
H-COM
input it will activate and deactivate the Heating mode, in such a way that
they will be managed remotely and automatically (
"AUTO"
mode), from the location where the
thermostat is installed.
The
C
,
H
and
COM
terminals are supplied from the factory with a jumper between each of them, so it
will be necessary to remove
both
jumpers before connecting any of the configurations of room
thermostats planned.
Depending on the type of the room thermostat used or any combination of them, it will be possible to
install up to 4 different configurations of room thermostat installation. In the following sections they
are described the functioning and installation instructions for each configuration.
IMPORTANT: Before carrying out any work on the electrical installation of the heat pump,
always ensure it is disconnected from the mains.
E1L
E2L N C4L N C6L L G2S G3S
H COM
N C
N
E1L
E2L N C4L N C6L L G2S G3S
H COM
N C
N
Содержание DUAL CLIMA R
Страница 1: ...DUAL CLIMA R Air to Water Heat Pump EN INSTALLATION AND OPERATION INSTRUCTIONS ...
Страница 54: ...EN 54 DUAL CLIMA R 14 2 Dual Clima 6R ...
Страница 55: ...55 DUAL CLIMA R 14 3 Dual Clima 9R ...
Страница 56: ...EN 56 DUAL CLIMA R 14 4 Dual Clima 12R ...
Страница 57: ...57 DUAL CLIMA R 14 5 Dual Clima 16R ...
Страница 58: ...EN 58 DUAL CLIMA R 14 6 Dual Clima 19R ...
Страница 59: ...59 DUAL CLIMA R 14 7 Dual Clima 16RT ...
Страница 60: ...EN 60 DUAL CLIMA R 14 8 Dual Clima 19RT ...
Страница 69: ...69 DUAL CLIMA R DUAL CLIMA 9R ...
Страница 70: ...EN 70 DUAL CLIMA R DUAL CLIMA 12R ...
Страница 71: ...71 DUAL CLIMA R DUAL CLIMA 16R ...
Страница 72: ...EN 72 DUAL CLIMA R DUAL CLIMA 19R ...
Страница 73: ...73 DUAL CLIMA R DUAL CLIMA 16RT ...
Страница 74: ...EN 74 DUAL CLIMA R DUAL CLIMA 19RT ...
Страница 81: ...81 DUAL CLIMA R NOTES ...
Страница 82: ...EN 82 DUAL CLIMA R NOTES ...
Страница 83: ...83 DUAL CLIMA R NOTES ...