E09
Antifreeze function in Heating/Cooling
mode.
The antifreeze function in heating/cooling mode has been
activated twice in 90 minutes. Disconnect and reconnect the
power supply of the heat pump. If the alarm is triggered
persistently repeatedly, contact the nearest official Technical
Assistance Service.
E10
Antifreeze function in DHW mode.
The antifreeze function in DHW mode has been activated
twice in 60 minutes. Disconnect and reconnect the power
supply of the heat pump. If the alarm is triggered
persistently repeatedly, contact the nearest official Technical
Assistance Service.
E11
Indoor exchanger temperature probe
failure.
Open circuit or short circuit in the internal heat exchanger
temperature sensor. Contact your nearest official Technical
Assistance Service to have it replaced.
E12
Incorrect heat pump setting.
Check the SW1 of the control card and all parameters of the
Service Menu. Contact your nearest official Technical
Assistance Service to have it replaced.
E13
Incorrect heat pump setting.
Check the SW1 of the control card and all parameters of the
Service Menu. Contact your nearest official Technical
Assistance Service to have it replaced.
E14
Suction temperature probe failure.
Open or short circuit of the suction temperature probe.
Contact your nearest official Technical Assistance Service to
have it replaced.
E15
Discharge temperature probe failure.
Open circuit or short circuit of the discharge temperature
probe. Contact your nearest official Technical Assistance
Service to have it replaced.
E16
Room sensor failure.
Open circuit or short circuit in the room sensor. Contact your
nearest official Technical Assistance Service to have it
replaced.
E17
Failure to read the flow temperature probe
or antifreeze activated 3 times in 20
minutes.
Failure to read the flow temperature probe or antifreeze
activated 3 times in 20 minutes. Disconnect and reconnect
the power supply of the heat pump. If the alarm is triggered
persistently repeatedly, contact the nearest official Technical
Assistance Service.
E18
Low temperature difference between flow
and return.
Excessively low temperature difference between the flow
and return temperature probes. Check the installation and
disconnect and reconnect the power supply of the heat
pump. If the alarm is triggered persistently repeatedly,
contact the nearest official Technical Assistance Service.
F01
Voltage protection.
The voltage of the power supply is too high, too low, or
unstable. The heat pump will recover when the voltage is
within the value range allowed by the heat pump:
185-265 V AC for simple phase models
340-440 V AC for three phase models
F02
IPM PFC module failure.
Error in the IPM module or incorrect cable connection.
Disconnect and reconnect the power supply of the heat
pump. If the alarm is triggered persistently repeatedly,
contact the nearest official Technical Assistance Service.
F03
Abnormal stop of the compressor.
The compressor stops abnormally. Contact your nearest
official Technical Assistance Service.
Содержание DUAL CLIMA R
Страница 1: ...DUAL CLIMA R Air to Water Heat Pump EN INSTALLATION AND OPERATION INSTRUCTIONS ...
Страница 54: ...EN 54 DUAL CLIMA R 14 2 Dual Clima 6R ...
Страница 55: ...55 DUAL CLIMA R 14 3 Dual Clima 9R ...
Страница 56: ...EN 56 DUAL CLIMA R 14 4 Dual Clima 12R ...
Страница 57: ...57 DUAL CLIMA R 14 5 Dual Clima 16R ...
Страница 58: ...EN 58 DUAL CLIMA R 14 6 Dual Clima 19R ...
Страница 59: ...59 DUAL CLIMA R 14 7 Dual Clima 16RT ...
Страница 60: ...EN 60 DUAL CLIMA R 14 8 Dual Clima 19RT ...
Страница 69: ...69 DUAL CLIMA R DUAL CLIMA 9R ...
Страница 70: ...EN 70 DUAL CLIMA R DUAL CLIMA 12R ...
Страница 71: ...71 DUAL CLIMA R DUAL CLIMA 16R ...
Страница 72: ...EN 72 DUAL CLIMA R DUAL CLIMA 19R ...
Страница 73: ...73 DUAL CLIMA R DUAL CLIMA 16RT ...
Страница 74: ...EN 74 DUAL CLIMA R DUAL CLIMA 19RT ...
Страница 81: ...81 DUAL CLIMA R NOTES ...
Страница 82: ...EN 82 DUAL CLIMA R NOTES ...
Страница 83: ...83 DUAL CLIMA R NOTES ...