UG6951 / UG6952 / UG6954 / UG6955 / UG6956 / UG6957
SAFEMASTER PRO fieldbus modules
12
/
17
0265998 09.05.2017 LA822P
VISUALISATIONS
UG6951
CANopen
UG6952
PROFIBUS DP
UG6954
PROFINET
UG6955
Ethernet/IP
UG6956
EtherCAT
UG6957
USB
NORMAL OPERATION
Description
upper 4 LEDs
LED 1
LED 2
ON
GREEN
RUN
GREEN
IN FAIL
RED
EXT FAIL
RED
RED/GREEN RED/GREEN
Startup - Initial test
ON
ON
ON
ON
ON
ON
Waiting for configuration
ON
flashing
OFF
OFF
OFF
OFF
Configuration received
ON
ON
OFF
OFF
see the module tables
Table 6
FAULT STATE
Description
upper 4 LEDs
LED 1
LED 2
ON
GREEN
RUN
GREEN
IN FAIL
RED
EXT FAIL
RED
RED/GREEN RED/GREEN
Internal fault microcontroller
ON
OFF
2 flashes*
OFF
see the module tables
Internal failure
ON
OFF
3 flashes*
OFF
Configuration Error
ON
OFF
5 flashes*
OFF
BUS communication Error
ON
OFF
5 fla s h e s *
OFF
BUS communication interruption
ON
OFF
ON
OFF
Identical module detected
ON
OFF
5 flashes*
5 flashes
Table 7
* The LED frequency of flashing is: ON for 300ms and OFF for 400ms, with an interval between two sequences of 1s.
LED 1, 2