UG6951 / UG6952 / UG6954 / UG6955 / UG6956 / UG6957
SAFEMASTER PRO fieldbus modules
6
/
17
0265998 09.05.2017 LA822P
Index I/O 1
Index I/O 2
EXAMPLES OF DIAGNOSTICS
Example 1
Figure
2
In the example shown in Figure 2, Input 1 (connected to module UG6911.10) is tested with the UG6911.10-T1
test signal.
During wiring, the 24Vdc is connected to input 1 instead of the UG6911.10-T1 test signal.
-
The I/O index and Diagnostic code show the following values: 1 - 10 to indicate the diagnostics on
input 1 of module UG6911.10 (OUT_TEST error)
Example 2
Figure
3
In this example, the I/O index corresponds to the logical block and not to the physical terminal on module
UG6911.10.
In Figure 3 for example, the two-hand element connected to the Input 1 and Input 2 physical terminals
corresponds to I/O index No. 1 and the emergency stop connected to the Input 3 and Input 4 terminals
corresponds to I/O index No. 2.