UG6951 / UG6952 / UG6954 / UG6955 / UG6956 / UG6957

 

SAFEMASTER  PRO fieldbus modules

 

6

/

17

 

 

0265998     09.05.2017    LA822P 

 

 

Index I/O 1 

Index I/O 2 

 

EXAMPLES OF DIAGNOSTICS 

 

Example 1 

Figure 

2

 

In the example  shown in Figure 2, Input  1 (connected  to module  UG6911.10) is tested with  the UG6911.10-T1 
test signal. 
During wiring, the 24Vdc is  connected  to input  1 instead  of the  UG6911.10-T1 test signal. 

-

 

The I/O index and Diagnostic  code show the following  values:  1 - 10 to indicate the diagnostics on 
input  1 of module  UG6911.10 (OUT_TEST error) 

 

Example 2 

Figure 

 

In this  example,  the I/O index  corresponds  to the logical  block and not to the physical  terminal  on module 
UG6911.10. 

 

In Figure 3 for example, the two-hand element  connected to the Input 1 and Input 2 physical  terminals 
corresponds  to I/O index  No. 1 and the emergency  stop connected  to the Input  3 and Input 4 terminals 
corresponds  to  I/O index  No. 2. 

 

Содержание Safemaster Pro Series

Страница 1: ...O O r r i i g g i i n n a a l l m m a a n n u u a a l l...

Страница 2: ......

Страница 3: ...DUCTION 2 ELECTRICAL CONNECTIONS DIMENSIONS 2 PROTOCOL DATA PACKAGE COMPOSITION 3 DIAGNOSTICS 5 1 Byte I O index 5 2 Byte Diagnostic code 5 Inputs 5 Safety outputs OSSD 5 EXAMPLES OF DIAGNOSTICS 6 Exa...

Страница 4: ...O system These fieldbus modules have no influence on the safety functions of the configurable safety system SAFEMASTER PRO ELECTRICAL CONNECTIONS DIMENSIONS Each module is provided with four connector...

Страница 5: ...G6911 10 UG6916 10 UG6913 16 UG6913 08 UG6913 12 If several modules of the same type are installed the order follows the node number All safety outputs are summarised in 1 or 2 bytes depending on syst...

Страница 6: ...eldbus probes 2 bytes OUTPUTS OSSD max 2 bytes Index of I O DIAGNOSTICS 2 bytes see Table 2 3 Diagnostic code One input byte Fieldbus PLC to Fieldbus module must always be defined for the whished stat...

Страница 7: ...OUT_TEST error OUT_TEST failure on this input 11 0x0B Second input defective Redundancy check failed on input 12 OUT_TEST diagnostics OK 13 Output connected to other inputs Test output not connected...

Страница 8: ...ad of the UG6911 10 T1 test signal The I O index and Diagnostic code show the following values 1 10 to indicate the diagnostics on input 1 of module UG6911 10 OUT_TEST error Example 2 Figure 3 In this...

Страница 9: ...the UG6913 16 T1 test signal The I O index and Diagnostic code show the following values 1 10 OUT_TEST error to indicate the diagnostics on input 1 of module UG6913 16 Example 4 Figure 5 In the exampl...

Страница 10: ...at is transferred on the INRAIL Bus Module UG6957 The software allows the bi directional data transfer In this case the operator can set the state of the inputs Fieldbus Input directly from the comput...

Страница 11: ...tabs Figures 8 to 11 Start window diagnostic selection Baudrate not all module types Figure 7 Figure 8 Figure 9 Address selection UG6951 UG6952 UG6953 UG6956 UG6954 automatic address selection UG6955...

Страница 12: ...UG6911 10 Master Status is displayed green UG6911 10 active RUN red UG6911 10 not active e g in communication with SAFEMASTER PRO Designer Window area figure 14 shows the status of the in and outputs...

Страница 13: ...be Bit 8 is displayed as bit 0 of the second byte OSSD 1 is ON and connected to the second output pair of the control unit UG6911 10 terminals 9 and 10 Its status is displayed in section Status OSSD a...

Страница 14: ...F OFF OFF OFF Configuration received ON ON OFF OFF see the module tables Table 6 FAULT STATE Description upper 4 LEDs LED 1 LED 2 ON GREEN RUN GREEN I NF AI L RED E XT FAIL RED RED GREEN RED GREEN Int...

Страница 15: ...952 not initialized STATUS SETUP or NW_INIT GREEN flashing On line CLEAR GREEN Initialized End of initialization NW_INIT RED flashing 1 flash Parameterization error ref IEC 61158 6 GREEN flashing Init...

Страница 16: ...rors detected Table 11 UG6956 EtherCAT LED 1 STS LED 2 ERR STATE INDICATES DESCRIPTION STATE INDICATES DESCRIPTION OFF INIT INIT or no power OFF No error No error or no power green OPERATIONAL OPERATI...

Страница 17: ...ires or sleeve length 7 mm Wire fxing captive slotted screw M3 Tightening torque 0 5 0 6 Nm Operating temperature 10 55 C Storage temperature 20 85 C Relative humidity 10 95 Enclosure Electronic housi...

Страница 18: ...module for 2 proximity switches 1 TTL encoder 0066060 UG6917 112 speed monitoring module for 2 proximity switches 2 TTL encoder 0066061 UG6917 202 speed monitoring module for 2 proximity switches 1 HT...

Страница 19: ...UG6951 UG6952 UG6954 UG6955 UG6956 UG6957 SAFEMASTER PRO fieldbus modules 0265998 09 05 2017 LA822P 17 17 Declaration of conformity...

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ...TIONAL PRE OPERATIONAL state red flashing 2 flashes Watchdog timeout Synch manager watchdog timeout green flashing 1 flash SAFE OPERATIONAL SAFEOPERATIONAL state red Controller fault module in EXCEPTI...

Отзывы: