UG6951 / UG6952 / UG6954/ UG6955 / UG6956 / UG6957 

 

SAFEMASTER  PRO fieldbus modules

 

0265998    09.05.2017   LA 822P 

 

5

/

17

 

 

DIAGNOSTICS 

Each input  and safety output  is associated with  a relative  diagnostic  code. 
When the I/O is connected correctly the diagnostic  code is OK and is not exported to the fieldbus; 
if there is a problem  on the I/O, the system exports 2 bytes to the fieldbus with: 

-

 

the index of the I/O in question 

-

 

the related diagnostic  code 

 

1. Byte:  "I/O index" 

This field indicates the number used to identify  the I/O with a diagnostic  code other than OK. 
Possible values for this field  are shown in Table 2. 

 

TYPE OF SIGNAL 

I/O INDEX 

Input 

1-128 

Output 

192-255 

Table 

2

 

 

2. Byte: "Diagnostic  code" 

The "Diagnostic  code" field  indicates  the diagnostics  for the I/O. Possible values  for this field  are shown in the 
following  tables. 

 

Inputs 

Input di ag nos ti c s  

1 2 8   (0 x8 0 ) 

Input diagnostics OK 

 

Not in initial  position 

Both  switches have to go to rest condition 

Concurrent failed 

Both switches have to change state simultaneously 

Concurrent failed hand1 

Wrong connection  on one side of a two-hands switch 

Concurrent failed hand2 

Wrong connection  on one side of a two-hands switch 

invalid  switch position 

The selector  can't  have more  than one input set 

Switch  not connected 

The selector can't have any input set 

10 (0x0A) 

OUT_TEST error 

OUT_TEST failure  on this input 

11 (0x0B) 

Second  input defective 

Redundancy check failed  on input 

12 

OUT_TEST  diagnostics OK 

 

13 

Output connected to other  inputs 

Test output not connected to the right  input 

14 

Output OK  but input  connected to 24VDC 

Stuck input 

15 

Short  circuit  between  photocell  test and 
photocell input 

Photocell  response time  too  low 

16 

No  response from  photocell 

The test signal on the photocell emitter  is not seen on the receiver 

17 

Short  circuit  between photocells 

The test signal is present on two different  photcells 

18 

MAT disconnected 

Wrong mat  connection 

19 

Output inconsistent with  feedback 

The test signal on input is present on more  than one OUT_TEST 

20 

Connection incorrect 

The  test signal  is  present on more  than one input 

21 

Output stuck 

The  test signal  on the  input is  not present on the OUT_TEST 

22 (0x16) 

Second OUT_TEST  KO 

Redundancy check  failed  on OUT_TEST 

1 3 3   (0 x8 5 )*

)

 

TWO-HAND  concurrent failed 

Two-hands  switch  has to change  state simultaneously 

1 3 4   (0 x8 6 )*

)

 

Not started 

Start test failed 

1 3 7   (0 x8 9 )*

)

 

Waiting for restart 

The input has manual  reset and has not been restarted 

Ta b le  3 

*

)

  The diagnostic  133,  134 and 137 do not provide  visual  error message on the LED from SAFEMASTER  PRO  

 

Safety outputs  OSSD 

OSSD  Diagnostics 

OSSD  DIAGNOSTICS  OK 

 

ENABLE MISSING 

 

WAITING  FOR  RESTART OSSD 

 

FEEDBACK  K1/K2 MISSING 

 

WAITING  FOR  OTHER  MICRO 

Redundancy check failed  on OSSD 

Ta b le  4 

 

 

If there are more than one diagnostic  codes, the information  changes every 500ms. 

Содержание Safemaster Pro Series

Страница 1: ...O O r r i i g g i i n n a a l l m m a a n n u u a a l l...

Страница 2: ......

Страница 3: ...DUCTION 2 ELECTRICAL CONNECTIONS DIMENSIONS 2 PROTOCOL DATA PACKAGE COMPOSITION 3 DIAGNOSTICS 5 1 Byte I O index 5 2 Byte Diagnostic code 5 Inputs 5 Safety outputs OSSD 5 EXAMPLES OF DIAGNOSTICS 6 Exa...

Страница 4: ...O system These fieldbus modules have no influence on the safety functions of the configurable safety system SAFEMASTER PRO ELECTRICAL CONNECTIONS DIMENSIONS Each module is provided with four connector...

Страница 5: ...G6911 10 UG6916 10 UG6913 16 UG6913 08 UG6913 12 If several modules of the same type are installed the order follows the node number All safety outputs are summarised in 1 or 2 bytes depending on syst...

Страница 6: ...eldbus probes 2 bytes OUTPUTS OSSD max 2 bytes Index of I O DIAGNOSTICS 2 bytes see Table 2 3 Diagnostic code One input byte Fieldbus PLC to Fieldbus module must always be defined for the whished stat...

Страница 7: ...OUT_TEST error OUT_TEST failure on this input 11 0x0B Second input defective Redundancy check failed on input 12 OUT_TEST diagnostics OK 13 Output connected to other inputs Test output not connected...

Страница 8: ...ad of the UG6911 10 T1 test signal The I O index and Diagnostic code show the following values 1 10 to indicate the diagnostics on input 1 of module UG6911 10 OUT_TEST error Example 2 Figure 3 In this...

Страница 9: ...the UG6913 16 T1 test signal The I O index and Diagnostic code show the following values 1 10 OUT_TEST error to indicate the diagnostics on input 1 of module UG6913 16 Example 4 Figure 5 In the exampl...

Страница 10: ...at is transferred on the INRAIL Bus Module UG6957 The software allows the bi directional data transfer In this case the operator can set the state of the inputs Fieldbus Input directly from the comput...

Страница 11: ...tabs Figures 8 to 11 Start window diagnostic selection Baudrate not all module types Figure 7 Figure 8 Figure 9 Address selection UG6951 UG6952 UG6953 UG6956 UG6954 automatic address selection UG6955...

Страница 12: ...UG6911 10 Master Status is displayed green UG6911 10 active RUN red UG6911 10 not active e g in communication with SAFEMASTER PRO Designer Window area figure 14 shows the status of the in and outputs...

Страница 13: ...be Bit 8 is displayed as bit 0 of the second byte OSSD 1 is ON and connected to the second output pair of the control unit UG6911 10 terminals 9 and 10 Its status is displayed in section Status OSSD a...

Страница 14: ...F OFF OFF OFF Configuration received ON ON OFF OFF see the module tables Table 6 FAULT STATE Description upper 4 LEDs LED 1 LED 2 ON GREEN RUN GREEN I NF AI L RED E XT FAIL RED RED GREEN RED GREEN Int...

Страница 15: ...952 not initialized STATUS SETUP or NW_INIT GREEN flashing On line CLEAR GREEN Initialized End of initialization NW_INIT RED flashing 1 flash Parameterization error ref IEC 61158 6 GREEN flashing Init...

Страница 16: ...rors detected Table 11 UG6956 EtherCAT LED 1 STS LED 2 ERR STATE INDICATES DESCRIPTION STATE INDICATES DESCRIPTION OFF INIT INIT or no power OFF No error No error or no power green OPERATIONAL OPERATI...

Страница 17: ...ires or sleeve length 7 mm Wire fxing captive slotted screw M3 Tightening torque 0 5 0 6 Nm Operating temperature 10 55 C Storage temperature 20 85 C Relative humidity 10 95 Enclosure Electronic housi...

Страница 18: ...module for 2 proximity switches 1 TTL encoder 0066060 UG6917 112 speed monitoring module for 2 proximity switches 2 TTL encoder 0066061 UG6917 202 speed monitoring module for 2 proximity switches 1 HT...

Страница 19: ...UG6951 UG6952 UG6954 UG6955 UG6956 UG6957 SAFEMASTER PRO fieldbus modules 0265998 09 05 2017 LA822P 17 17 Declaration of conformity...

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ...TIONAL PRE OPERATIONAL state red flashing 2 flashes Watchdog timeout Synch manager watchdog timeout green flashing 1 flash SAFE OPERATIONAL SAFEOPERATIONAL state red Controller fault module in EXCEPTI...

Отзывы: