UG6951 / UG6952 / UG6954/ UG6955 / UG6956 / UG6957
SAFEMASTER PRO fieldbus modules
0265998 09.05.2017 LA 822P
7
/
17
Example 3
Figure
4
The example in Figure 4 is similar to example 1, except in this case Input1 is connected to module UG6913.16
and is tested with the UG6913.16-T1 test signal.
During wiring, the 24Vdc is connected to input 1 instead of the UG6913.16-T1 test signal.
-
The I/O index and Diagnostic code show the following values:
1 - 10
(OUT_TEST error) to indicate the
diagnostics on input 1 of module UG6913.16
Example 4
Figure
5
In the example shown in Figure 5 the manual reset function is enabled on OSSD 1.
The E-Stop-button connected to input 1 is released without sending a reset command.
-
The I/O index and Diagnostics code show the following values:
192 - 2
-
to indicate the OSSD 1A/1B (Table 2: 192 = first output).
-
to indicate the diagnostic code (Table 4: 2 = Waiting for OSSD to restart).