Environmental and Power Requirements
Environmental
Specifications
Table 1–2 describes the environmental specifications for your
system.
Table 1–2 Environmental Specifications
Specification
Measurement
Operating temperature
10-35° C (50-95° F)
Relative humidity (noncondensing)
20-80%
Maximum heat dissipation
Single power supply
2390 Btu/hr
Dual power supply
4097 Btu/hr
Minimum operating clearance
Front
75 cm (29.5 in)
Rear
15 cm (5.9 in)
Maximum operating altitude
2000 m (6562 ft)
Maximum current rating
Single power supply
8.0/4.0 A
Dual power supply
4.6/2.2 A
Operating voltage range (single
phase)
100–120/
220–240 VAC
Operating frequency range
50 Hz to 60 Hz
Power cord length
190 cm (75 in)