3
Functions of Devices in DVP-PM
DVP-PM Application Manual
3-47
Y
X
Block A
Block B
Path with smooth transition
Path with a right-angle turn
Function Group:
Setting up Percentage Value of G-Code Moving Speed
Number:
D1798
Explanations:
1. When D1798 is set to 100, the G-Code moving speed will be the original speed. When D1798 is set to 1,000, the
G-Code moving speed will become 10 times faster than the original speed. When D1798 is set to 50, the G-Code
moving speed will decrease to half of the original speed, and so forth.
2. The upper limit of G-Code moving speed is 500k(Hz). When the G-Code moving speed is set to be faster than
500k(Hz), the speed will be set as 500k(Hz) automatically
Function Group:
Setting up Input Terminal Polarity (for X/Y-axis)
Number:
D1799
Explanations:
For input terminals below, setting the corresponding bit# to be ON will define the input terminal as NO contact; setting
the corresponding bit# to be OFF will define the input terminal as NC contact.
20PM:
bit#
Input terminal polarity on X axis
bit#
Input terminal polarity on Y axis
0 PG0 8 PG01
1 MPGB0
9 MPGB1
2 MPGA0 10
MPGA1
3 LSN0 11 LSN1
4 LSP0
12
LSP1
5 DOG0
13
DOG1
6 STOP0
14
STOP1
7 START0
15
START1
10PM:
bit#
Input terminal polarity
0 DOG0
Содержание DVP-10PM
Страница 1: ......
Страница 45: ...2 Hardware Specifications and Wiring DVP PM Application Manual 2 30 MEMO...
Страница 125: ...3 Functions of Devices in DVP PM DVP PM Application Manual 3 80 MEMO...
Страница 341: ...8 Application Examples DVP PM Application Manual 8 2 Trajectory 3 Trajectory 4...
Страница 427: ...9 Electrical CAM DVP PM Application Manual 9 74...
Страница 437: ...10 Encrypting User Program DVP PM Application Manual 10 10 MEMO...
Страница 458: ...11 G code Application DVP PM Application Manual 11 21 B O100 main program...
Страница 561: ...14 Appendix DVP PM Application Manual 14 4 MEMO...