Categories and Use of Basic Application Instructions
DVP-PM Operation Instruction
5-66
API Mnemonic
Operands
Function
46
ANS
P
Timed Annunciator Set
Controllers
20PM
10PM
Bit Devices
Word devices
Program Steps
Type
OP
X Y M S K H KnX
KnY
KnM KnS T C D E F
S
*
m
*
D
*
ANS: 7 steps
Operands:
S
: Alarm timer
m
: Time setting
D
: Alarm
Explanations:
1.
ANS instruction is used to drive the output alarm device in designated time.
2. Operand
S
valid range: T0~T183
Operand
m
valid range: K1~K32,767 (unit: 100 ms)
Operand
D
valid range: S912~S1023
3.
Flag: M1048 (ON: Alarm is active), M1049 (ON: Alarm monitoring is enabled)
4.
See ANR instruction for more information
Program Example:
If X3 = ON for more than 5 sec, alarm step relay S999 will be ON. S999 will remains ON after X3 is reset. (T10 will
be reset, present value = 0)
X3
ANS
T10
K50
S999